Specifications
Installation
outSide FreSh-air connection:
This Heater must have adequate air for proper combustion in the room that it is installed.
A Fresh-air intake is strongly recommended for all installations. Failure to install intake air may 
Figure 7: Outside Air Connection. 
exhauSt and FreSh air intake locationS:
result  in  improper  combustion  as  well  as  the  unit  smoking 
during power failures. 
The inlet to the intake must be below and a minimum of 12” 
(30cm) away from the unit exhaust outlet. 
Outside  fresh  air  is  mandatory  when  installing  this 
unit in airtight homes and mobile homes.
When connecting to an outside fresh air source, do not use 
plastic or combustible pipe.  A 3” minimum  (76 mm) ID (inside 
diameter) steel, aluminum or copper pipe or ducting should 
be used. The inlet must have a rodent screen installed. It is 
recommended, when you are installing a fresh air system, to 
keep the number of bends in the pipe to a minimum. 
3" ID
(76 mm)
Optional
Elbow
Outside
Wall
9
14 
3
/16"
(361mm)
5 
1
/8"
(130mm)
4 
3
/16"
(107mm)
Figure 8: Maxx-M Inlet and Outlet Location. 
This unit uses a 4” exhaust vent.
EXHAUST:
Base of unit to center of flue
 min. 14
3
/
16”  (361 mm)
Center of unit to center of flue
  4
3
/
16”  (107 mm)
FRESH AIR INTAKE.
Base of unit to center of intake
 min. 14
3
/
16”  (361 mm)
Center of unit to center of intake
  5⅛”  (130 mm)