Datasheet
Page9of43
RF‐PS‐500 SSK routers are used in conjunction with the Sontay® RF‐RXSS receiver, RF‐TS‐900 nodes and RF‐
HHT hand heldmonitor,and are used toroute signalsfrombatterypowered nodesand other routers to the
receivermodule,wherethesignalstrengthofadirectpath
isnotsufficientforreliablecommunications.
NB Each router can support a maximum of 16 “children”, which can consist of a maximum of 8 battery
powered nodes and 8 routers, or up to 16 routers if there are no battery powered end devices (EDs).
Considerationshouldbegivenonnetwork
planningforredundancyincaseofrouterfailureordamage.
Routersautomaticallyfindthebestpathbacktothereceiver,whichmaybedirectlytothereceiverorviaother
“parent”routers.
NB To preserve battery life, an SSK router will automatically go off‐line after approximately 4 hours if
not
power‐cycled.
TochargethebatteryinanSSK router,connectthecorrectchargertothesocketmountedonthesideof the
housing.ThestatusLEDonthechargerwillshowreduntilthebatteryisfullycharged,whenthestatusLEDwill
turngreen.NB‐thesame
chargertypeisusedforbothSSKnodesandSSKrouters.
To power an SSK router, the battery must be connected and the On/Off toggle switch on the housing side
shouldbe switchedto theOn position.Toswitch off,theOn/Off toggleswitch onthe housingsideshouldbe
switchedtotheOffposition.Refertodatasheet.
• SSKroutersdonothaveatemperaturesensorfitted.
SSKRouterSpecification:
RadioOutput:
Frequency 2.4GHz
16channels,automaticallyselected
Direct‐sequencespreadspectrum
Compliance IEEE802.15.4‐2006
AerialCharacteristics
Gain 2.0dBi
VSWR <2:1
DataEncryption: AES
128
PowerOutput: +10dBm(10mW@50Ω)
BatteryType: 3.7VLithiumPolymer,rechargeable,1080mAh
Housing:
Material ABS(flameretardanttypeVO)
Dimensions 55mmx90mmdia.
Mountingholes4mmspaced85mmapart
Environmental:
Operating:
Temperature‐10°Cto+50°C
RH 0to90%,non‐condensing
Storage:
Temperature‐
10°Cto+80°C
RH 0to90%,non‐condensing
Countryoforigin: UK
PartCode:RF‐PS‐500
Refertoproductdatasheetforinstallationinstructions.