Datasheet
Page8of43
SSKNodes
RF‐TS‐900 nodes are used in conjunction with the Sontay® RF‐RXSS receiver, RF‐PS‐500 routers and RF‐HHT
handheldmonitor.
Data is transmitted back to the receiver every 30 seconds. Each sensor retains these configurations if the
batterybecomesdischargedorrequiresreplacement.
NB‐To preserve battery life, an SSK node will automatically go off‐line after approximately 4 hours if not
power‐cycled.
TochargethebatteryinanSSKnode,connectthecorrectchargertothesocketonthebackplate.Thestatus
LEDonthechargerwillshowreduntil
thebatteryisfullycharged,whenthestatusLEDwillturngreen.
TopoweranSSKnode,thebatterymustbeconnectedandtheOn/Offrockerswitchonthebackplateshould
beswitchedtotheOnposition.Toswitchoff,theOn/Offrockerswitchonthebackplateshouldbeswitched
to
theOffposition.Refertodatasheet.
Thesensorsautomaticallyfindthebestpathbacktothereceiver,whichmaybedirectlytothereceiverorvia
“parent”routers.
• SSKnodeshaveathermistortemperaturesensorfittedasstandard.
SSKNodeSpecification:
RadioOutput:
Frequency 2.4GHz
16channels,automaticallyselected
Direct‐sequencespreadspectrum
Compliance IEEE802.15.4‐2006
AerialCharacteristics
Gain 1.2dBi
VSWR 1.5:1
DataEncryption: AES128
PowerOutput: 0dBm(1mW@50Ω)
Temperatureaccuracy ±0.3°C
BatteryType: 3.7VLithiumPolymer,rechargeable,1080mAh
HousingMaterial: ABS(flameretardant)
Dimensions: 85x85
x23mm
Environmental:
Operating:
Temperature‐10°Cto+50°C
RH 0to90%,non‐condensing
Storage:
Temperature‐10°Cto+80°C
RH 0to90%,non‐condensing
Countryoforigin: UK
PartCode:RF‐TS‐900
Refertoproductdatasheetforinstallationinstructions.
SSKRouters