SHERWOOD INDUSTRIES IS AN ENVIRONMENTALLY RESPONSIBLE COMPANY. THIS MANUAL IS PRINTED ON RECYCLED PAPER. PLEASE KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE Kodiak Wood Stove BY: SHERWOOD INDUSTRIES LTD OWNER’S MANUAL Models: 1200 & 1700 Insert and 1200 & 1700 Fireplace Freestanding INSTALLER: Leave this manual with the wood stove. CONSUMER: Retain this manual for future reference.
Table of Contents Safety Precautions.............................................................................................3 Operating Instructions........................................................................................4 Building Your Fire...................................................................................6 Air Control.............................................................................................9 How It Works................................................
Safety Precautions FOR SAFE INSTALLATION AND OPERATION OF YOUR “ENVIRO” WOOD STOVE, PLEASE CAREFULLY READ THE FOLLOWING INFORMATION: ● Please read this entire manual before you install and use your new woodstove. Failure to follow instructions may result in property damage, bodily injury or even death. Be aware that local Codes and Regulations may override some items in this manual. Check with your local inspector.
Operating Instructions FIRST START When first installed, the chimney, firebricks and steel are cold and it usually takes several hours on a fairly high burn for them to become hot and dry enough for the stove to function well. We recommend during the unit’s first burn that a door and window are opened to vent the smoke and fumes created from the unit’s paint curing. The paint will smell a little for the first burn or two as it cures.
Operating Instructions 1. Plug the fan assembly into a standard three (3) prong grounded electrical receptacle. 2. Freestanding - turn the rotary fan controller to the desired setting. Inserts - an auto/off/manual rocker switch allows the fan to be turned on manually, or automatically. When this switch is pushed right toward the unit, it will be set to manual operation; the center position is off, and when pushed left away from the unit, it will be set to automatic. 3.
Operating Instructions FAILURE TO INSPECT AND CLEAN YOUR CHIMNEY SYSTEM REGULARLY CAN RESULT IN A CHIMNEY FIRE, WHICH COULD DAMAGE THE CHIMNEY OR CAUSE A HOUSE FIRE. CHIMNEY OR RUN AWAY FIRE: 1. Call local fire department (or dial 911) 2. Close the draft fully 3. Examine the flue pipes, chimney, attic, and roof of the house, to see if any part has become hot enough to catch fire. If necessary, spray with fire extinguisher or water from the garden hose. 4.
Operating Instructions a) Before attempting to add fuel to the stove, OPEN the damper control fully by pulling it all the way out. This allows the chimney to carry away the additional smoke, which occurs when the door is open. b) DO NOT OVERLOAD THE STOVE. Normally, three or four logs will provide heat for several hours. Never operate this stove where portions glow red hot. c) DO NOT OVERFIRE. If the heater or chimney connector glows, you are overfiring.
Operating Instructions 2. What type of wood is best to use as firewood? Both hardwood and softwood burn well in this stove. Both woods contain about 8,000 BTU/lb (18,570 KJ/Kg), but hardwood is generally more dense, will weigh more per cord, and burns a little slower and longer. Cutting firewood so that it will fit horizontally, front to back, makes it easier loading and less likely for the fuel to roll on the glass. Except for a cold start, there is no need to crisis-cross the logs.
Operating Instructions 8. What can cause a poor draft? The most common factors for poor draft are: a) Air supply b) Environmental conditions c) Cold chimney temperature d) Poor chimney installation and maintenance e) Atmospheric pressure a) Air supply – Inside the home, normal household appliances such as clothes dryers and forced-air furnaces compete for air, resulting in air starvation to the fire. This creates a condition in the house known as negative pressure.
Operating Instructions HOW IT WORKS: Smoke 1/2" Ceramic baffle; reflects heat down to burn up smoke. Primary air; window airwash. Secondary air tubes; creates a secondary burn on the particles in the smoke. Pilot air. Dry seasoned wood Slider plate; used for air flow control. Intake air. Intake air. Figure 4: 1200 Air Flow Path. Smoke 1/2" Ceramic baffle; reflects heat down to burn up smoke. Primary air; window airwash.
Specifications 1200 SPECIFICATIONS: Table 1: 1200 General Information. Model 1200 Freestanding Flat Top Width x Depth 1200 Insert Step Top 25” x 22 7/16” (635 mm x 570 mm) Height with pedestal or legs 28 1⁄4” (718mm) 31 1⁄4” (794 mm) Height of body 18 1⁄4” (464 mm) 21 1⁄4” (540 mm) Fire box size 273⁄4” x 211⁄2” (705 mm x 546 mm) 191/16” (484 mm) or 199/16” (497 mm) 16.1” x 18.25” x 11.15” (409 mm x 464 mm x 283 mm) (depth x width x height) 1.85 feet3 (0.
Specifications 1700 SPECIFICATIONS: Table 2: 1700 General Information. Model 1700 Freestanding Flat Top Width x Depth 25” x 26 Step Top 15/16” (635 mm x 684 mm) Height with pedestal or legs 28 1⁄4” (718mm) 31 1⁄4” (794 mm) Height of body 18 1⁄4” (464 mm) 21 1⁄4” (540 mm) Fire box size (depth x width x height) 273⁄4” x 26” (705 mm x 660 mm) 191/16” (484 mm) or 199/16” (497 mm) 20.65” x 18.25” x 11.95” (525 mm x 464 mm x 304 mm) 2.5 feet3 (0.
Specifications CLEARANCES TO COMBUSTIBLES - 1200 INSERT: A Minimum clearance to an unshielded side wall 10” (254 mm) B Minimum clearance to an unshielded 8” (203 mm) mantel 21” (533 mm) C Minimum top facing (protruding 3⁄4” [19 mm]) clearance 171⁄2” (445 mm) D Minimum side facing (protruding 3⁄4” [19 mm]) clearance 1” (25 mm) �������� ���� Table 3: 1200 Insert Clearance to Combustibles.
Specifications CLEARANCES TO COMBUSTIBLES - 1700 INSERT: A Minimum clearance to an unshielded side wall 10” (254 mm) B Minimum clearance to an unshielded 8” (203 mm) mantel 24” (610 mm) C Minimum top facing (protruding 3⁄4” mm]) clearance [19 D Minimum side facing (protruding 3⁄4” mm]) clearance [19 191⁄2” (495 mm) 1” (25 mm) E † From front of door opening to edge of floor protection USA 16” (406 mm) CND 18” (450 mm) F † From side/back of unit to edge of floor protection USA 6” (152 mm) CN
Specifications CLEARANCES TO COMBUSTIBLES - 1200 FREESTANDING: MAINTAIN THESE MINIMUM CLEARANCES TO UNSHIELDED COMBUSTIBLES* �������� ���� � � ����� � � � ����� � ������ ���� ���� � ������ ������ ���� ���� � � � �� �� � ���� ���� � �������� ���� ���� ���� � � � J � � ����� I ������ Table 9: 1200 Freestanding Clearance to Combustibles. Single Wall Pipe Double Wall Pipe** Double Wall Pipe with Heat Efficiency Shield 50-1088 (Flat top model only) Top vent out back wall with min.
Specifications CLEARANCES TO COMBUSTIBLES - 1700 FREESTANDING: MAINTAIN THESE MINIMUM CLEARANCES TO UNSHIELDED COMBUSTIBLES* �������� ���� � � ����� � � � � ������ ���� ���� � ����� � � ������ ������ ���� ���� � �� �� � ���� ���� � �������� ���� ���� ���� � � � J � � ����� I ������ Table 10: 1700 Freestanding Clearance to Combustibles. Single Wall Pipe Double Wall Pipe** Double Wall Pipe with Heat Efficiency Shield 50-1088 (Flat top model only) Top vent out back wall with min.
Specifications DIMENSIONS - 1200 INSERT: 267/8" (683mm) 229/16" (574mm) 221/4" (566mm) 273/4" (705mm) 337/8" (860mm) 205/16" (516mm) 461/8" (1171mm) Min 131/4" (337mm) Max 1415/16" (380mm) 5" (127mm) 161/2" (419mm) Regular Surround 2715/16" (709mm) Oversized Surround 333/16" (709mm) 191/16" (484mm) or 199/16" (497mm) 2011/16" (525mm) 191/16" (484mm) or 199/16" (497mm) 183/8" (467mm) 19" (482mm) 227/8" (580mm) 3/16" (5mm) Figure 6: 1200 Insert Dimensions.
Specifications DIMENSIONS - 1700 INSERT: 2615/16" (684mm) 241/4" (566mm) 273/4" (705mm) 337/8" (860mm) 461/8" (1171mm) 2413/16" (630mm) Min. 173/4" (452mm) Max. 197/16" (495mm) 5" (127mm) 21" (533mm) Regular Surround 2715/16" (709mm) Oversized Surround 333/16" (709mm) 191/16" (484mm) or 199/16" (497mm) 2011/16" (525mm) 191/16" (484mm) or 199/16" (497mm) 183/8" (467mm) 231/2" (596mm) 273/8" (695mm) 3/16" (5mm) Figure 7: 1700 Insert Dimensions.
Specifications DIMENSIONS - 1200 FREESTANDING: 22 7/16" 25" (570mm) 5 15/16" (635mm) 6 1/16" 16 1/2" (151mm) (153mm) (419mm) 30 1/4" 9 15/16" (769mm) (252mm) 15 13/16" (402mm) 29 15/16" (760mm) 28 1/4" 20" (508mm) 3 (718mm) 7/8" (98mm) 10" (254mm) Legs same height 14 3/4" 24 3/8" (375mm) 26 (619mm) 3/8" (670mm) Figure 8: 1200 Freestanding Flat Top Dimensions.
Specifications DIMENSIONS - 1700 FREESTANDING: 25" 26 (635mm) 15/16" 19 3/8" (684mm) 5 15/16" (492mm) 21" (151mm) 6 1/16" (534mm) (153mm) 15 7/8" 9 15/16" (403mm) (252mm) 30 1/4" (769mm) 28 1/4" (718mm) 10" (254mm) Pedestal same height 23 1/16" (586mm) 24 1/2" 25 15/16" 3 7/8" (622mm) (659mm) (98mm) Figure 10: 1700 Freestanding Flat Top Dimensions.
Specifications FREESTANDING SIDE DIMENSIONS FOR FAN KIT: �� ������� � ���� ������� � ���� ������ �� ���� ������� Figure 12: 1200 Freestanding with Fan Kit Dimensions. �� ���� ��� � ���� ���� ��� �� ���� ���� ��� � ����� ���� ��� Figure 13: 1700 Freestanding with Fan Kit Dimensions.
Installation Please read and understand these instructions before installing pedestal or ash pan and leg option. Failure to follow these instructions carefully could cause personal injury or property damage. All screws are pre-installed on the base of the unit. REMOVAL FROM PALLET: • Remove the bricks from the unit before starting. • Remove the two (2) lag bolts (shown in Figure 1) that secure the unit to the pallet from inside the firebox.
Installation LEGS AND ASH PAN INSTALLATION - FREESTANDING: • Place the unit on the pallet on its back.
Installation MODIFICATIONS FOR INSTALLATION WITH 191/16” (484MM) HIGH LINTEL - INSERT The Kodiak has a factory height of 199/16” (497mm) and it can be reduced to 191/16” (484mm) by modifying the unit and the surround panel. Surround Panel: 1. Fasten the Surround Spacer to the inner top surface of the Surround Panel using the four (4) T-20 screws (refer to Figure 19). 2. Refer to INSTALLATION OF THE SURROUND PANEL - INSERT to finish assembling the surround panel.
Installation HEARTH PROTECTION EXAMPLES: Table 11: Examples of Hearth Pad Sizing Using Clearances From Tables 9 &10 (refer to Figures 22 & 23).
Installation H D USA 6" (152mm) CND 8" (203mm) Optional Coverage F L USA 6" (152mm) CND 8" (203mm) O N USA 6" (152mm) CND 8" (203mm) P B J USA 16" (406mm) CND 18" (457mm) B Door Opening E Optional Coverage M C G A I K USA 6" (152mm) CND 8" (203mm) Door Opening USA 16" (406mm) CND 18" (457mm) G Figure 22: General Parallel Installation (refer to Tables 11 & 12). Optional Coverage E A C Figure 23: General Corner Installation (refer to Tables 11 & 13).
USA 1700 Canada USA 1200 Canada USA 1700 Canada USA 1200 Canada Double 1200 Canada Wall Pipe with Heat USA Efficiency Shield 501700 Canada 1088 (Flat top model USA only) Double Wall Pipe Single Wall Pipe (K) Front of Hearth Pad to Corner 613⁄8” (1558mm) 593⁄8” (1507mm) 671⁄4” (1708mm) 651⁄4” (1657mm) 597⁄8” (1522mm) 577⁄8” (1471mm) 651⁄8” (1654mm) 631⁄8” (1603mm) 597⁄8” (1522mm) 553⁄4” (1417mm) 643⁄8” (1636mm) 595⁄8” (1514mm) 575⁄8” (1465mm) 547⁄8” (1393mm) 617⁄8” (1571mm) 59” (1499mm) 565⁄8” (14
Installation OUTSIDE AIR KIT: It is mandatory to use outside air for installations in mobile homes. ���� �� �������� A 4” (10.2 cm) fresh air adaptor kit is available. This adaptor can be installed either on the back pedestal or through the floor under the pedestal. The cover plate must be installed on the unit if your stove is located in a mobile home or if using outside air from the bottom. Place the 1⁄4” mesh screen between the fresh air adaptor and the body of the pedestal (as shown to right).
Installation CHIMNEY INSTALLATION THROUGH WALL: Here are four (4) methods of combustible wall chimney connector pass-throughs. Information was provided from NFPA 211. Minimum chimney clearance to brick and combustibles 2 inches (50.8 mm) } Chimney Flue Minimum clearance 12 inches (304.8 mm) of brick Chimney connector Fire clay liner } Minimum 12 inches (304.8 mm) to combustibles Masonry chimney Figure 26: Chimney Through Wall - Method A.
Installation INSTALLATION OF A LISTED, FACTORY BUILT CHIMNEY - FREESTANDING: This is a generic set of instructions; always follow the chimney manufacturer’s instructions explicitly. Also refer to “RECOMMENDED HEIGHTS FOR FLUE PIPE”. 1. 2. 3. 4. 5. 6. 7. 8. 9. 30 Set floor protector and stove in location in accordance with the “CLEARANCES TO COMBUSTIBLES - 1200 FREESTANDING” or “CLEARANCES TO COMBUSTIBLES 1700 FREESTANDING”. 2 ft (0.
Installation and in any area within 10 feet Rain cap/ Spark arrestor cap (304.8 cm) of the roof ridge, the chimney must be 2 feet Storm Collar Roof radiation (60.9 cm) above the ridge. Roof flashing shield (if required) Refer to Figure 30. Roof Note: Increasing the chimney Insulated chimney height above the roof may help your unit to draft better.
Installation MASONRY CHIMNEY INSTALLATION - FREESTANDING: DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE. A non-combustible floor protector is required under all freestanding units; refer to “CLEARANCES TO COMBUSTIBLES - 1200 FREESTANDING” or “CLEARANCES TO COMBUSTIBLES - 1700 FREESTANDING”. When venting into a masonry chimney, the floor protector must be installed directly below the chimney vent and 2” (50.8 mm) on either side of the chimney vent.
Installation MASONRY FIREPLACE INSTALLATION - FREESTANDING: Rain Cap Steel Plate or Flashing Chimney Support and Clamp Unless you are experienced, we recommend installation by your dealer or a professional installer. Many venting manufacturers have listed kits available to connect a stove to a masonry fireplace. Always follow the vent manufacturer’s installation instructions. Rigid Stainless Steel Liner The existing damper may have to be removed to allow installation.
Installation These connectors must be installed in accordance with the manufacturer’s instructions. Use only specified components. The chimney and pipe must extend at least 10 feet (2.4 m) above the stove and 3 feet (0.9 m) above the highest point of the roof. Install a rain cap with spark arrestor at the top that will not impede the smoke exhaust. The chimney must be supported at the ceiling or roof so that its weight will not sit on the stove.
Installation MASONRY FIREPLACE INSTALLATION - INSERT: Unless you are experienced, we recommend installation by your dealer or a professional installer. Install only in a masonry fireplace with a good-condition chimney at least 15 ft (4.6 m) high, both of which have been constructed in accordance with the building code. Refer to Tables 5 and 8 for minimum masonry fireplace dimensions. Be sure the fireplace and chimney are clean and sound without any cracks or loose mortar.
Installation The flue collar is removable for installations into fireplaces with low openings. USA 16” (406 mm) CND 18” (450 mm) Floor Protection Masonry Fireplace 8" (203 mm) Combustible Floor Figure 38: Insert Installation into existing fireplace without hearth. a) Remove the rear two (2) secondary air tube and C-Cast Ceramic Baffles, if installed (see C-CAST CERAMIC BAFFLE INSTALLATION).
Installation Figure 41: Removable flue collar in place. 4. Screw or nail the provided metal plate with the wording “THIS FIREPLACE HAS BEEN ALTERED TO ACCOMMODATE A FIREPLACE INSERT AND SHOULD BE INSPECTED BY A QUALIFIED PERSON PRIOR TO THE RE-USE AS A CONVENTIONAL FIREPLACE.” to the inside of the fireplace. Leveling Legs Figure 42: Leveling legs.
Installation INSTALLATION USING A BLOCK-OFF PLATE FOR USA ONLY - INSERT: If this unit is to be installed into a masonry fireplace or a zero-clearance fireplace with a direct connection you must install a non-combustible seal-off device such as a block-off plate or damper adapter. By installing a block-off plate you seal the chimney, ensuring that no smoke enters the home and sealing the chimney to encourage draft. To construct a block-off plate follow the below steps. 1.
Installation 5. Mount the block-off plate using masonry screws in a masonry fireplace and sheet metal screws on a zeroclearance fireplace (screws need only be long enough to penetrate the first layer of metal). 6. Insulate the block-off plate using high - temperature fiberglass insulation and furnace cement. Mantel Damper must be removed Stainless steel chimney connector must extend 12" (305mm) past the block-off plate. Block-off plate or damper adaptor.
Installation MODEL 1200 BRICK PLACEMENT & TUBE LOCATIONS: COMPLETE THE STOVE AND SMOKE PIPE INSTALLATION BEFORE PLACING THESE BRICKS. Tube E Tube D Tube A ick Br l a e rti S iz l Pa l Fu rick B lf Ha rick B 1. Place the three (3) full size bricks along each side of the firebox and one (1) full size brick on either side of the back of the firebox. 2. To place the floor bricks, lay the two (2) partial bricks along the back of the floor.
Installation MODEL 1700 BRICK PLACEMENT & TUBE LOCATIONS: COMPLETE THE STOVE AND SMOKE PIPE INSTALLATION BEFORE PLACING THESE BRICKS. Tube C Tube B Tube A ick al Br Parti rick ize B Ful l S Half ck Bri 1. Place the four (4) full size bricks along each side of the firebox and one (1) full size brick on either side of the back of the firebox. 2. To place the floor bricks, lay the two (2) partial bricks along the back of the floor.
Installation DOOR INSTALLATION: Please inspect all components for damage. If damage has occurred, please contact the courier company, dealer, or distributor and have components repaired or replaced before installation. Remove the door from the packaging. Inspect the door assembly for damage. 1. Install door handle as shown in Figure 50. Nut Cast Latch Washer (x2) Spring Washer Furel Handle Figure 50: Installation Door Handle Hardware. 2.
Installation C-CAST CERAMIC BAFFLE INSTALLATION: 1. Slide the right C-Cast Ceramic Baffle in over the secondary air tubes at the top of the firebox. The tab must be on the top and pointing towards the center and the smooth side is to face down. 2. Hook the outside edge of the baffle over the top of the secondary air chamber. This will make room to for the installation of the left C-Cast Ceramic Baffle. 3. Slide the left C-Cast Ceramic Baffle in over the secondary air tubes.
Installation Fan Black White Black White Fan controller Fan temperature sensor Power Supply Figure 54: Freestanding Fan Kit Wiring Diagram. Fan Black Fan temperature sensor Black Rocker Switch Manual Black Off Auto Black Black Black Black White Fan controller Power Supply Figure 55: Fireplace Insert Fan Kit Wiring Diagram.
Installation OPTIONAL FAN INSTALLATION - FREESTANDING: Refer to FAN WIRING DIAGRAM before installing your optional fan kit. 1. Remove the fan assembly from the box and inspect for any damage to the assembly. If damage is noticed call your dealer, distributor or courier company and have components replaced before installing kit. 2.
Installation FIREPLACE POKER HANGERS - FREESTANDING: When the fireplace poker is not in use it can be hung at the back of the unit on either side. Figure 58: Fireplace poker hanging. REMOVAL OF THE SHROUDS - INSERT: A 1. If the surround panel is installed, remove it by lifting the panel straight up then out. B 2. For the right shroud, twist the handle on the air control clockwise to remove it from the rod. 3. Pull unit forward a few inches, if possible. 4.
Installation INSTALLATION OF THE SURROUND PANEL - INSERT: Installation of Trim: The trim set for your surround panel must be installed before installing the surround panel onto the unit, if not already done. 1. Attach one side trim to the top trim, using a corner bracket (see Figure 60) to secure pieces together. There are two (2) main pieces to each corner bracket (see Figure 61).
Rating Label Tested & Listed By C O-T L Beaverton Oregon USA US OMNI-Test Laboratories, Inc, Certified for use in Canada & USA / Certifié pour installation au Canada et aux Etats-Unis. DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE LISTED SOLID FUEL SPACE HEATER / IDENTIFIE COMME UN FOYER A COMBUSTIBLE SOLIDE Model / Modèle: Report/Rapport no.
Parts List Reference # Description Part # 1 120°F (49°C) Ceramic Fan Temperature Sensor EC-001 2 Insert Burner Switch EC-026 3 FPI Fan Controller - 115V EC-039 3 Fan Controller Knob EC-040 4 Domestic power cord - 115V EC-042 Heyco Strain Relief EC-044 Door Gasket - 7 feet (2.
Parts List Reference # 50 Description Part # 24 Pumice Bricks - 41⁄2” X 9” (114mm x 229mm) 50-1105 25 Pumice Bricks - 41⁄2” X 41⁄2” (114mm x 114mm) 50-1106 26 1200 & 1700 Cast Ash Plug 50-1120 27 Door Handle Assembly (Rod, Cast Latch, Brass Spring) 50-1121 27 1200 & 1700 Cast Latch 50-1381 28 Wood Door Glass Retainer Kit (With Screws) 50-1122 29 1200 Freestanding Flat Top Left Side Cabinet 50-1123 30 1200 Freestanding Flat Top Right Side Cabinet 50-1124 31 1200 Freestanding Step
36 29 32 16 March 2008 Kodiak - Freestanding Components 35 31 32 33 46 30 19 20 9 18 45 26 23 24 18 22 21 25 43 50 44 28 5 17 8 15 7 27 1 3 10 Parts Diagram - Freestanding 51
Parts Diagram - Pedestals & Legs March 2008 12 Kodiak - Pedestal and Leg Kit Components 40 38 42 14 11 6 41 39 37 13 52
4 49 2 1 55 53 3 52 56 54 48 March 2008 9 16 47 57 Kodiak - Fireplace Insert Components Parts Diagram - Fireplace Insert Common parts are shown in Parts Diagram - Freestanding.
Warranty Sherwood Industries Ltd. is the manufacturer of the Enviro line of heating products. At Sherwood Industries, our commitment to the highest level of quality and customer service is the most important thing we do. Each Enviro stove is built on a tradition of using only the finest materials and is backed by our Exclusive Lifetime Limited Warranty to the original purchaser. With Enviro, you’re not just buying a stove, you’re buying a company with years of unequalled performance and quality.
Warranty 6. If the problem is not covered by the Limited Warranty, the customer will be responsible for all repair costs, as well as all storage, shipping and the cost of removing and re-installing the stove. If you are not satisfied with the service provided by the Enviro dealer, write to Sherwood Industries Ltd. at the address listed on the last page of the Owner’s Manual. Include the date you bought the product and a description of the problem. Exclusions and Limitations: 1.
Warranty 12. The Limited Warranty does not cover damage caused by burning salt-saturated wood, corrosive driftwood, chemically treated wood or any fuel not recommended in the Owner’s Manual (use cord wood only). The Limited Warranty is void if: a) The stove has been operated in atmospheres contaminated by chlorine, fluorine or other damaging chemicals. b) The stove is subject to submersion in water or prolonged periods of dampness or condensation.
Warranty 26. Sherwood Industries Ltd. is not liable for freight or labour on any stove replaced in-field and is not liable for travel costs for service work. In the event of in-home repair work, the customer will pay any in-home travel fees or service charges required by the Authorized Dealer. 27. At no time will Sherwood Industries Ltd. be liable for any consequential damages which exceed the purchase price of the unit. Sherwood Industries Ltd.
Installation Data Sheet The following information must be recorded by the installer for warranty purposes and future reference.