Part Number 22744 We Manage Heat ® Installation and Operation Manual Environmental Technology, Inc. 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239 FAX (574) 233-2152 or (888) 234-4238 http://www.networketi.com/ 22804 11/07 (800) 234-4239 http://www.networketi.com Environmental Technology, Inc.
Model SST–2 2 of 12 Environmental Technology, Inc. http://www.networketi.
Model SST–2 Safety Make all electrical connections in compliance with the National Electric Code (NFPA 70) and local electrical code. If you have questions concerning the installation or application, contact Customer Service. Additional Information More information is regularly made available through our website, www.networketi.com. Please visit us online for datasheets, manuals, white papers, technical articles and more.
Model SST–2 Front Panel Interface Status indicator Remote Interface Alarm relay Summary alarms Control Supply voltage Contact type Maximum Ratings Temperature Sensor Set point Dead band Sensor type Circuit type Lead Length SUPPLY (green) power applied SUPPLY (green, flashing) bad thermistor HEAT (yellow) call for heat GFEP (red) ground fault condition GFEP (red, flashing) failed GFEP test GFEP (red, flashing, rapid) GFEP test in progress Isolated SPDT 1 AMP Class 2 contact No Power Ground Fault Condition G
Model SST–2 Initial Inspection Inspect the SST for shipping damage. If any of the following problems are found contact the Customer Service Department. • Contents incomplete or incorrect • Internal or external mechanical damage Customer service is available between 8:00 a.m. and 5:00 p.m. ET at (574) 233-1202 or (800) 234-4239. In the event of shipping damage, keep the packing materials for inspection by the carrier. Normally, Environmental Technology, Inc.
Model SST–2 Figure 2: SST–2 wiring. See Appendix B.
Model SST–2 NEC Class 2 Low Voltage Connections All low voltage wiring shall use 18 AWG or greater stranded conductors with thermoplastic insulation rated for at least 75°C (194°F) at 300 VAC. The temperature sensor is supplied with a 20' (6m) 2-wire jacketed cable lead. The temperature sensor lead may be up to 500' (152.4m) using 18 AWG 2-wire jacketed cable, or up to 2,000' (609.6m) using 12 AWG 2-wire jacketed cable. Temperature Sensor The Temperature Sensor is required for the operation of the SST.
Model SST–2 remains. The ground fault condition will be persistent and will be remembered by the SST even if the unit loses power. To clear the ground fault condition momentarily press the GFEP TEST/RESET switch on the SST. Maintenance The SST–2 does not require routine maintenance. For technical help, questions or comments concerning this product or any Environmental Technology, Inc.
Model SST–2 Appendix A. SST–2 Dimensions. 7 7/16" (189mm) 1 1/16” (27mm) Conduit Entry 4 1/4" (108mm) 1 1/16” (27mm) Conduit Entry 20' (6m) Sensor Cable, 3/16" (5mm) Ø 3/8" (10mm) Ø Temperature Sensor 1 7/16" (37mm) 22804 11/07 (800) 234-4239 http://www.networketi.com Environmental Technology, Inc.
Model SST–2 Appendix B. SST–2 Wiring Diagram. 10 of 12 Environmental Technology, Inc. http://www.networketi.
Model SST–2 Appendix C. SST–2 Wiring. 22804 11/07 (800) 234-4239 http://www.networketi.com Environmental Technology, Inc.
Model SST–2 ORDERING INFORMATION Order Number 22744 19272 Description Model SST–2 Freeze Protection Thermostat Temperature Sensor (included) LIMITED WARRANTY ETI’s two year limited warranty covering defects in workmanship and materials applies. Contact Customer Service for complete warranty information. DISCLAIMER Environmental Technology, Inc.