Specifications
Electrical connection 
The SILENT is an extractor designed for a single phase supply, with voltage and 
frequency as indicated on the rating plate of the unit. The units are manufactured with 
double  electrical  insulation  (Class  II)  and  therefore  they  do  not  need  an  earth 
connection. 
The electrical installation must include a double pole switch with a contact clearance of 
at least 3 mm. 
The electrical cable must enter the SILENT through the cable entry (4). 
The SILENT must be connected to the electrical supply in accordance with local wiring 
regulations. 
Once  the  cable  has  been  introduced  proceed  using the  electrical  wiring  diagram 
applicable to the selected model. 
SILENT S 
For these models use the following diagrams: 
Fig.3: Switching the extractor through the light switch. 
Fig.4: To switch the fan through an independent switch. 
SILENT T 
This model is  provided  with an adjustable  over-run timer. The timer allows  the fan to 
continue to operate for the selected period after the switch has been turned off (fig.6). 
Fig.5 shows  how  to connect  the  fan  with  timer  utilising  the  same  switch  as  for  the 
lighting circuit. 
To set the timer, turn the potentiometer on the printed circuit board as (fig. 7). 
- To reduce the "run on" time, turn anticlockwise (min. 1 minute) 
- To increase the "run on" time, turn clockwise (max: 30 minutes). 
SILENT-100 IT (this version is only available as SILENT-100) 
This model is  provided  with an adjustable  over-run timer. The timer allows  the fan to 
continue to operate for the selected period after the switch has been turned off (fig.6). 
ATTENTION: The product  also  includes an  over-run timer  facility that 
starts the fan after the first 50 seconds of non-operation. After these first 50 
seconds the fan operates automatically. 
SILENT HT 
IMPORTANT: 
Do not remove the tape covering the humidity sensor located on the reserve 
of the grille. 
Models provided with an electronic humidistat which can be adjusted from 60% to 90 % 
RH (relative humidity) and with a timer, adjustable between 2 and 20 minutes. 
Operation 
Case 1: Automatic operation (fig.9) 
In  automatic  operation,  the  humidistat  causes  the  extractor  to  operate  automatically 
when the humidity level in the room is higher than the set level. The extractor will stop 
automatically when the humidity drops below the selected level and after the selected 
period set on the timer. 
Case 2: Automatic operation as in case 1 with the facility to override the humidistat by 
means of the light switch (fig.8), when the humidity level in the room is lower than the 