Installation manual
17
ENVISION AIR HANDLER INSTALLATION MANUAL
ECM Blower Control
The ECM blower motor is controlled by an interface board 
installed in the air handler and allows field selectable CFM 
settings. The interface board receives inputs from the 
thermostat and converts them to signals used by the ECM 
motor. There are four different airflow settings that are field 
selectable via DIP switches (see Blower Performance table).
Cooling/Heating settings
The cooling/heating CFM settings determine the 
normal cooling/heating CFM when the unit is not in 
dehumidification mode or auxiliary heat mode. DIP switches 
1 and 2 ‘off’ is the lowest CFM setting while with DIP 
switches 1 and 2 ‘on’ is the highest CFM setting. To prevent 
air coil freeze up, the lowest CFM setting can not be used 
when dehumidification mode is selected. DIP 9 must be ‘on’ 
to enable normal airflow settings.
Dehumidification Mode settings
This setting provides for field selection of humidity control 
(via setting DIP 9 ‘off’). The cooling airflow settings are 
determined by the Cooling/Heating DIP switch settings 
above. Dehumidification mode reduces the selected normal 
cooling CFM by 15%-20% which increases the moisture 
removing capability of the heat pump. To prevent air coil 
freeze up, the lowest CFM setting can not be used when 
dehumidification mode is selected.
Dehumidification Mode (Continuous) – This mode is 
selected via setting DIP 9 ‘off’ on the ECM interface board 
and will be engaged whenever an ‘O’ input is present. In this 
mode any time the unit is operating in cooling mode, it will 
run at a CFM level 15%-20% lower than the selected normal 
cooling CFM.
NOTE: Do not select dehumidification mode if the lowest 
Cooling/Heating airflow level is selected (DIPS 1 & 2 off).
Auxiliary Heat settings - DIP 5 and 6 on the ECM interface 
board are used to select the desired CFM in auxiliary/
emergency heat mode. Whenever auxiliary or emergency 
electric heat is energized this air flow setting will be used.
NOTE: DIP switches 3, 4, 7, 8, and 10 are not used.










