General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage
wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable. See unit electri-
cal data for fuse or cicuit breaker sizing information.
Electrical Data
Thermostat Wiring
Figure 12: Thermostat Wiring, Single and Dual Capacity Units
Electrical Data
HWA Ext Total Min Max
Pump Loop Unit Circ Fuse/
MCC RLA LRA FLA FLA FLA Amp HACR
022 208-230/60/1 197/253 14.0 9.0 48.0 0.4 5.4 14.8 17.1 25
030 208-230/60/1 197/253 20.0 12.8 58.3 0.4 5.4 18.6 21.8 30
036 208-230/60/1 197/253 22.0 14.1 73.0 0.4 5.4 19.9 23.4 35
042 208-230/60/1 197/253 26.0 16.6 79.0 0.4 5.4 22.4 26.6 40
048 208-230/60/1 197/253 31.0 19.8 109.0 0.4 5.4 25.6 30.6 50
060 208-230/60/1 197/253 41.2 26.4 134.0 0.4 5.4 32.2 38.8 60
070 208-230/60/1 197/253 47.0 30.1 158.0 0.4 5.4 35.9 43.4 70
026 208-230/60/1 197/253 16.0 10.2 52.0 0.4 5.4 16.0 18.6 25
038 208-230/60/1 197/253 26.0 16.6 82.0 0.4 5.4 22.4 26.6 40
049 208-230/60/1 197/253 33.0 21.1 96.0 0.4 5.4 26.9 32.2 50
064 208-230/60/1 197/253 40.0 25.6 118.0 0.4 5.4 31.4 37.8 60
072 208-230/60/1 197/253 42.5 27.2 150.0 0.4 5.4 33.0 39.8 60
Notes:
Rated Voltage of 208-230/60/1. HACR circuit breaker in USA only. Min/Max Voltage of 197/253. All fuses Class RK-5.
Rev.: 02/20/07
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Field low voltage point to point wiring:
From
Thermostat
To Air Handler
To Compressor
Section
C C C
R R R
G G
O O O
Y1 Y1 Y1
Y2 Y2 Y2
W2 W
L L
Air Handler transformer must be 75VA.
5/29/08