Installation manual

9
ENVISION SERIES INSTALLATION MANUAL
Air Handler Physical Data
1/11/08
Line Set Sizes
AirHandlerModelNumber(Refrigerant) NAH022 NAH026 NAH030 NAH036 NAH042 NAH048 NAH060
Evaporator Coil
Air Coil Total Face Area, ft2 [m2] 5.83 [0.54]
Tube outside diameter - in. [mm] 3/8 [9.52]
Number of rows 2 3
Fins per inch 12
Suction line connection - in. [mm] sweat 5/8 [15.87] 7/8 [22.22]
Liquid line connection - in. [mm] sweat 3/8 [9.52]
Refrigerant R-410a
Nominal cooling capacity - tons [kW] 1.8 [6.44] 2.1 [7.59] 2.5 [8.79] 3 [10.55] 3.5 [12.30] 4 [14.06] 5 [17.58]
Condensate drain connection - (FPT) in. [mm] 3/4 [19.05]
Blower Wheel Size (Dia x W), in. [mm] 11 x 10 [279 x 254]
Blower motor type/speeds ECM variable speed
Blower motor output - hp [W] 1/2 [373] 1 [746]
Filter Standard - 1” [51mm] MERV3 disposable, in. [mm] 20 x 24 [508 x 635]
Electrical characteristics (60hz) 208/230 - 1ph
Shipping weight - lbs. [kg] 205 210
Operating weight - lbs. [kg] 195 [88.45] 200 [90.71]
Unit
Size
Air
Handler
20feet 40feet 60feet
NZFactory
Charge(oz.)
*InitialSystem
Charge(oz.)
Suction Liquid Suction Liquid Suction Liquid
NSZ022 NAH022 5/8” OD 3/8” OD 5/8” OD 3/8” OD 3/4” OD 3/8” OD 56 88
NSZ030 NAH030 5/8” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 3/8” OD 56 88
NSZ036 NAH036 5/8” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 1/2” OD 56 96
NSZ042 NAH042 3/4” OD 3/8” OD 3/4” OD 3/8” OD 7/8” OD 1/2” OD 74 109
NSZ048 NAH048 3/4” OD 3/8” OD 7/8” OD 3/8” OD 7/8” OD 1/2” OD 90 125
NSZ060 NAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 92 132
NSZ070 NAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 108 152
NDZ026 NAH026 5/8” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 1/2” OD 52 84
NDZ038 NAH036 5/8” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 1/2” OD 56 96
NDZ049 NAH048 3/4” OD 3/8” OD 7/8” OD 3/8” OD 7/8” OD 1/2” OD 90 125
NDZ064 NAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 92 132
NDZ072 NAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 104 152
5/28/08
NOTES: *Initial System Change includes Factory Split charge + 20’ lineset charge + required additional charge, then adjust
charge by subcooling and superheat measurements.
If lineset is longer than 20’, then the additional charge for R-410A is 0.50 oz. per ft. for 3/8” and 1.0 oz. per ft. for 1/2” tube.