Water Piping
Piping is usually design as ‘reverse return’ to equalize flow
paths through each unit. A short flexible pressure rated
hose is used to make connection to the fixed building
piping system. This hose is typically stainless steel braid
and includes a swivel fitting on one end for easy removal
and is flexible to help isolate the unit for quieter operation
. Isolation valves for servicing, y-strainers for filtering
and memory-stop flow valve or a balancing valve can be
provided for consistent water flow through the unit.
All unit source water connections are fittings that accept
a male pipe thread (MPT). Insert the connectors by
hand, then tighten the fitting with a wrench to provide
a leakproof joint. The open and closed loop piping
system should include pressure/temperature ports for
serviceability. The proper water flow must be provided to
each unit whenever the unit operates. To assure proper
flow, use pressure/temperature ports to determine the
flow rate. These ports should be located at the supply
and return water connections on the unit. The proper
flow rate cannot be accurately set without measuring the
water pressure drop through the refrigerant-to-water heat
exchanger. Never use flexible hoses smaller than 1˝ inside
diameter on the unit. Limit hose length to 10 feet per
connection. Check carefully for water leaks.
Condensate Drain
On vertical units, the internal condensate drain assembly
consists of a drain tube which is connected to the drain
pan, a 3/4˝ PVC female adapter and a flexible connecting
hose. The female adapter may exit either the front or
the side of the cabinet. The adapter should be glued to
the field-installed PVC condensate piping. On vertical
upflow units, a condensate hose is inside all cabinets as a
trapping loop; therefore, an external trap is not necessary.
On horizontal units, a PVC stub is provided for condensate
drain piping connection. An external trap is required (see
below). If a vent is necessary, an open stand pipe may be
applied to a tee in the field-installed condensate piping.
Envision Application Notes cont.
1.5 in.
1.5 in.
3/4 in. PVC tube stub
3/4 in. PVC
Coupling
Vent (if needed)
3/4 in. PVC
1/8 in. per foot