Hanger Bracket Locations
Operating Limits
(°F) (°C) (°F) (°C)
Air Limits
Min. Ambient Air 45 7.2 45 7.2
Rated Ambient Air 80 26.7 70 21.1
Max. Ambient Air 100 37.8 85 29.4
Min. Entering Air 50 10.0 40 4.4
Rated Entering Air db/wb 80.6/66.2 27/19 68 20.0
Max. Entering Air db/wb 110/83 43/28.3 80 26.7
Water Limits
Min. Entering Water 30 -1.1 20 -6.7
Normal Entering Water 50-110 10-43.3 30-70 -1.1
Max. Entering Water 120 48.9 90 32.2
Notes:
Cooling Heating
Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy
temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The
operating limits are dependant upon three primary factors: 1) water temperature, 2) return air temperature, and 3)
ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be
at the normal level for proper and reliable unit operation.
Operating Limits
3/8" Threaded
Rod (by others)
Hex Nuts (2)
(by others)
Washer
Vibration
Isolator
Bolt and
Lock Washer
A
24.8
27.8
27.8
27.8
25.1
25.1
Model
022 - 030*
036 - 038
042 - 049
060 - 072
009 - 012*
015 - 018*
Hanger Kit
Part Number
995500A04
995500A03
995500A03
995500A03
995500A04
995500A04
B
63.4
72.4
77.4
82.4
44.7
53.7
C
21.1
24.1
24.1
24.1
21.4
21.4
D
N /A
43.1
48.1
53.1
N /A
N /A
E
N /A
29.3
29.3
29.3
N /A
N /A
F
1.1
1.1
1.1
1.1
1.3
1.3
NOTE: *Only the four corner brackets are needed on sizes 009-030.
C
F
B
Air Coil
Air Coil
D
E
A