Specifications

41
ENVISION COMMERCIAL SPECIFICATION CATALOG
Electrical Data
ECM Motor
CAUTION: When installing a unit with an ECM blower motor in 460/60/3 voltage, a neutral wire is required to allow proper
unit operation.
Model
Rated
Voltage
Voltage
Min/Max
Compressor Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC RLA LRA LRA**
NS015
208-230/60/1 197/253 na 6.2 29.0 n/a 4.0 10.2 11.8 15
265/60/1 238/292 na 5.6 28.0 n/a 4.1 9.7 11.1 15
NS018
208-230/60/1 197/253 na 8.4 33.5 n/a 4.0 12.4 14.5 20
265/60/1 238/292 na 7.3 28.0 n/a 4.1 11.4 13.2 20
NS022
208-230/60/1 197/253 14.0 9.0 48.0 17.0 4.0 13.0 15.2 20
265/60/1 238/292 13.0 8.3 40.0 n/a 4.1 12.4 14.5 20
NS030
208-230/60/1 197/253 20.0 12.8 58.3 21.0 4.0 16.8 20.0 30
265/60/1 238/292 14.9 9.5 87.0 n/a 4.1 13.6 16.0 25
NS036
208-230/60/1 197/253 22.0 14.1 73.0 26.0 4.0 18.1 21.6 35
265/60/1 238/292 17.5 11.2 60.0 n/a 4.1 15.3 18.1 25
208-230/60/3 187/253 13.9 8.9 58.0 n/a 4.0 12.9 15.1 20
460/60/3 414/506 6.5 4.2 28.0 n/a 4.1 8.3 9.4 10
NS036*
208-230/60/1 197/253 22.0 14.1 73.0 26.0 7.0 21.1 24.6 35
265/60/1 238/292 17.5 11.2 60.0 n/a 6.9 18.1 20.9 30
208-230/60/3 187/253 13.9 8.9 58.0 n/a 7.0 15.9 18.1 25
460/60/3 414/506 6.5 4.2 28.0 n/a 6.9 11.1 12.2 15
NS042
208-230/60/1 197/253 26.0 16.6 79.0 28.0 4.0 20.6 24.8 40
208-230/60/3 187/253 16.3 10.4 73.0 n/a 4.0 14.4 17.0 25
460/60/3 414/506 9.0 5.8 38.0 n/a 4.1 9.9 11.3 15
NS042*
208-230/60/1 197/253 26.0 16.6 79.0 28.0 7.0 23.6 27.8 40
208-230/60/3 187/253 16.3 10.4 73.0 n/a 7.0 17.4 20.0 30
460/60/3 414/506 9.0 5.8 38.0 n/a 6.9 12.7 14.1 15
NS048
208-230/60/1 197/253 31.0 19.8 109.0 38.0 4.0 23.8 28.8 45
208-230/60/3 187/253 21.2 13.6 83.1 n/a 4.0 17.6 21.0 30
460/60/3 414/506 9.5 6.1 41.0 n/a 4.1 10.2 11.7 15
NS048*
208-230/60/1 197/253 31.0 19.8 109.0 38.0 7.0 26.8 31.8 50
208-230/60/3 187/253 21.2 13.6 83.1 n/a 7.0 20.6 24.0 35
460/60/3 414/506 9.5 6.1 41.0 n/a 6.9 13.0 14.5 20
NS060
208-230/60/1 197/253 41.2 26.4 134.0 47.0 7.0 33.4 40.0 60
208-230/60/3 187/253 24.9 15.9 110.0 n/a 7.0 22.9 26.9 40
460/60/3 414/506 12.1 7.7 52.0 n/a 6.9 14.6 16.6 20
NS070
208-230/60/1 197/253 47.0 30.1 158.0 55.0 7.0 37.1 44.6 70
208-230/60/3 187/253 32.0 20.5 155.0 n/a 7.0 27.5 32.6 50
460/60/3 414/506 15.0 9.6 75.0 n/a 6.9 16.5 18.9 25
ND026
208-230/60/1 197/253 16.0 10.2 52.0 18.0 4.0 14.2 16.8 25
ND038
208-230/60/1 197/253 26.0 16.6 82.0 29.0 4.0 20.6 24.8 40
208-230/60/3 187/253 17.4 11.1
58.0 n/
a 4.0 15.1 17.9 25
460/60/3 414/506 7.0 4.5 29.0 n/a 4.1 8.6 9.7 10
ND038*
208-230/60/1 197/253 26.0 16.6 82.0 29.0 7.0 23.6 27.8 40
208-230/60/3 187/253 17.4 11.1 58.0 n/a 7.0 18.1 20.9 30
460/60/3 414/506 7.0 4.5 29.0 n/a 6.9 11.4 12.5 15
ND049
208-230/60/1 197/253 33.0 21.1 96.0 34.0 4.0 25.1 30.4 50
208-230/60/3 187/253 21.0 13.4 88.0 n/a 4.0 17.4 20.8 30
460/60/3 414/506 10.0 6.4 41.0 n/a 4.1 10.5 12.1 15
ND049*
208-230/60/1 197/253 33.0 21.1 96.0 34.0 7.0 28.1 33.4 50
208-230/60/3 187/253 21.0 13.4 88.0 n/a 7.0 20.4 23.8 35
460/60/3 414/506 10.0 6.4 41.0 n/a 6.9 13.3 14.9 20
ND064
208-230/60/1 197/253 40.0 25.6 118.0 41.0 7.0 32.6 39.0 60
208-230/60/3 187/253 27.5 17.6 123.0 n/a 7.0 24.6 29.0 45
460/60/3 414/506 14.0 9.0 62.0 n/a 6.9 15.9 18.1 25
ND072
208-230/60/1 197/253 42.5 27.2 150.0 53.0 7.0 34.2 41.0 60
5/6/09
HACR circuit breaker in USA only
* With optional 1 HP ECM2 motor
** With optional IntelliStart
TM
, only available on 208-230/60/1