Specifications

43
ENVISION COMMERCIAL SPECIFICATION CATALOG
Auxiliary Heat Ratings
Auxiliary Heat Electrical Data
KW BTU/HR Min
Model 208V 230V Stages 208V 230V CFM 009-012 015 018 022 026 - 030 036 - 042 048 - 072
EAS(H)4 2.9 3.8 1 9,700 12,900 250
EAM(H)5 3.6 4.8 1 12,300 16,300 450
EAM(H)8 5.7 7.6 2 19,400 25,900 550
EAM(H)10 7.2 9.6 2 24,600 32,700 650
EAL(H)10 7.2 9.6 2 24,600 32,700 1100
EAL(H)15 10.8 14.4 3 36,900 49,100 1250
EAL(H)15-3 10.8 14.4 3 36,900 49,100 1250
EAL(H)20 14.4 19.2 4 49,200 65,500 1500
NOTE: "H" is used in part number for horizontal units
Envision Series Compatibility
(208-230V & Premier Control Only)
(208-230V & Premier Control Only)
Supply
Circuit 208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V Min AWG Max FT
EAS(H)4 Single 13.7 15.8 17.9 20.5 20 20 20 20 20 20 12 80
EAM(H)5 Single 17.3 20 26.7 30 30 30 30 30 30 30 10 90
EAM(H)8 Single 27.5 31.7 39.3 44.6 40 45 40 45 40 50 6 140
EAM(H)10 Single 34.7 40 48.3 55 50 60 50 60 50 60 6 120
EAL(H)10 Single 34.7 40 53.3 60 60 60 60 60 60 60 6* 110
Single 52.0 60 75 85 80 90 80 90 70 100 4* 120
L1/L2 34.7 40 53.3 60 60 60 60 60 60 60 6* 110
L3/L4 17.3 20 21.7 25 25 25 25 25 20 30 10 100
Single 69.3 80 96.7 110 100 110 100 110 100 100 2* 140
L1/L2 34.7 40 53.3 60 60 60 60 60 60 60 6* 110
L3/L4 34.7 40 43.3 50 45 50 45 50 40 50 6 130
Supply Wire
EAL(H)15
Heater Amps Min Circuit Amp Max Fuse (USA) Max Fuse (CAN)
Model
EAL(H)20
Max CKT BRK