Power Capacitors B25667B4197A375
Power Factor Correction PhaseCap MKK400-D-10-01/MKK415-D-10.4-01
Edition 3.
FK PFC RD / VA 20.10.05
Page 1 of 3
Construction Dimensional drawing
Dielectric: Polypropylene film
Gas-impregnated / dry type
Concentric winding
Wave cut
Extruded round aluminum can with stud
Provided with ceramic discharge module
Triple safety system
Features
Three phase, delta connected
Self-healing technology
Naturally air cooled (or forced air cooling)
Indoor mounting
Typical applications
For Power Factor Correction
Terminals
SIGUT terminals
Mounting parts
Threaded stud at bottom of can
(
max. torque = 10 Nm for M12)
Technical data and specifications
Characteristics MKK400-D-10-01 MKK415-D-10.4-01
Rated capacitance C
R
3 x 64 µF 3 x 64 µF
Tolerance -5 / +10% -5 / +10%
Connection D (Delta) D (Delta)
Rated voltage V
R
400 VAC 415 VAC
Rated frequency f
R
50 Hz 60 Hz 50 Hz 60 Hz
Output 10 kvar 12 kvar 10.4 kvar 12.5 kvar
Rated current I
R
14 A 17 A 15 A 17 A