Datasheet

2-line filters B84142B*R000
for converters and power electronics
Typical circuit diagram
L
LINE
LOAD
L’
N N’
SSB0772-K
Technical data and measuring conditions
Rated voltage V
R
250 V DC/AC, 50/60 Hz
Rated current I
R
Referred to 40 °C ambient temperature
Test voltage V
test
1770 V DC, 2 s (line/line)
2700 V DC, 2 s (lines/case)
Overload capability (thermal) 1.5 · I
R
for 3 min per hour or
2.5 · I
R
for 30 s per hour
Leakage current l
leak
At 250 V AC, 50 Hz
Climatic category (IEC 60068-1) 25/100/21 (–25 °C/+100 °C/21 days damp heat test)
Approvals EN 133200
Characteristics and ordering codes
V
R
AC/DC
I
R
Terminal
cross section
I
leak
R
typ
Approx.
weight
Ordering code Approvals
V
A
mm
2
mA m kg
250 8 4 < 3.5 42 1.35 B84142B0008R000 ×
12 4 < 3.5 30 1.45 B84142B0012R000 ×
16 4 < 3.5 21 1.45 B84142B0016R000 ×
25 10 < 3.5 9 3.7 B84142B0025R000 ×
× = approval granted
Please read Cautions and warnings and
Important notes at the end of this document.
01/06 3