Datasheet

3-line filters B84143A*R000
for converters and power electronics
Typical circuit diagram
L1
LINE
SSB0797-6
LOAD
L1’
L2 L2’
L3
L3’
Technical data and measuring conditions
Rated voltage V
R
480/275 V AC, 50/60 Hz
Rated current I
R
Referred to 40 °C ambient temperature
Test voltage V
test
1770 V DC, 2 s (line/line)
2700 V DC, 2 s (lines/case)
Overload capability (thermal) 1.5 · I
R
for 3 min per hour or
2.5 · I
R
for 30 s per hour
Leakage current I
leak
At 400 V AC, 50 Hz
Climatic category (IEC 60068-1) 25/100/21 (–25 °C/+100 °C/21 days damp heat test)
Approvals UL 1283 for 440/250 V AC
Please read Cautions and warnings and
Important notes at the end of this document.