Datasheet
1-line filters B85321A*A630, A101 … A501
Feedthrough filters
∅ 55 mm, 63 … 500 A
Feedthrough filters ∅ 55 mm
Technical data and measuring conditions
Rated voltage V
R
250 V AC, 50/60 Hz
350 and 600 V DC
Rated current I
R
Referred to 40 °C ambient temperature
Reduced current values at 400 Hz
Capacitance tolerance ±20%
Climatic category (IEC 60068-1) 40/085/56 (–40 °C/+85 °C/56 days damp heat test)
Screw cap fixing Standard M32 × 1.5
Special fixing M27 × 1.5 for filters up to 300 A on request
Approvals UL 1283, 250 V
Characteristics and ordering codes
I
R
A
C
R
µF
V
R
V AC
V
R
V DC
V
test
V DC
Terminal Dimensions (mm) Ordering code Approvals
l +1 l
1
–1 l
2
–3
63 2 × 0.5 250 600 3000 M6 100 166 45 B85321A2105A630 ×
2 × 1.0 250 600 2500 M6 100 166 45 B85321A2205A630 ×
2 × 2.0 250 600 2500 M6 100 166 45 B85321A2405A630 ×
2 × 4.7 250 350 1700 M6 100 166 45 B85321A2945A630 ×
100 2 × 0.5 250 600 3000 M8 100 180 52 B85321A2105A101 ×
2 × 1.0 250 600 2500 M8 100 180 52 B85321A2205A101 ×
2 × 2.0 250 600 2500 M8 100 180 52 B85321A2405A101 ×
2 × 4.7 250 350 1700 M8 100 180 52 B85321A2945A101 ×
200 2 × 0.5 250 600 3000 M10 100 185 55 B85321A2105A201 ×
2 × 1.0 250 600 2500 M10 100 185 55 B85321A2205A201 ×
2 × 2.0 250 600 2500 M10 100 185 55 B85321A2405A201 ×
2 × 4.7 250 350 1700 M10 100 185 55 B85321A2945A201 ×
300 2 × 0.5 250 600 3000 M12 100 195 60 B85321A2105A301 ×
2 × 1.0 250 600 2500 M12 100 195 60 B85321A2205A301 ×
2 × 2.0 250 600 2500 M12 100 195 60 B85321A2405A301 –
2 × 4.7 250 350 1700 M12 100 195 60 B85321A2945A301 ×
400 2 × 0.5 250 600 3000 M16 130 245 72 B85321A2105A401 –
2 × 1.0 250 600 2500 M16 130 245 72 B85321A2205A401 –
2 × 2.0 250 600 2500 M16 130 245 72 B85321A2405A401 –
2 × 4.7 250 350 1650 M16 130 245 72 B85321A2945A401 –
× = approval granted
Please read Cautions and warnings and
Important notes at the end of this document.
01/06 11