Datasheet

54
Pleas e read Important notes on page 4 and Cautions and warnings on page 69.
B i tte beachten Sie d i e S e i te 4 Wichtige Hinweise s owi e d i e
Warn- und Sicherheitshinweise auf S e i te 69.
© EPCOS AG 2008
AC Power Line Series
Protection class I & II
V13... D20... L1... H3...
Type L10-A800XP1 H30-E800XP
Ordering code B88069X5451B201 on request
V13-A500XN V13-A800XN D20-A800XP L1B-A800XP1 H38-E800XP
B88069X6940C251 B88069X4380C251 on request B88069X6551B201 B88069X6821B101
Protection class I & II I & II I & II II
Application for N-PE N-PE PD N-PE N-PE
Nom. DC spark-over 500 800 800 800 800 V
voltage V
sdcN
DC spark-over voltage 500 ... 850 > 600 > 550 > 600 > 600 V
Impulse spark-over voltage @ 1.2/50 µs, < 1300 < 1500 < 1500 < 1500 < 1500 V
6 kV for 99% of measured values
(combination wave generator
[
2
Ω
Ω
])
Class I
Max. continuous operating voltage
@ 50/60 Hz 255 255 255 255 255 V
Nominal discharge current 8/20 µs 40 40 20 50 100 kA
Impulse current 10/350 µs 12 12 25 50 100 kA
Follow current @ 50/60 Hz 100 100 100 100 100 A
Class II
Max. continous operating voltage
@ 50/60 Hz 255 255 255 ––V
Nominal discharge current 8/20 µs 40 40 20 kA
Max. discharge current 8/20 µs 60 60 40 kA
Follow current @ 50/60 Hz 100 100 100 A
AC discharge current 300 300 –300 300 A
(TOV at 1200 V)
1 operation 50 Hz, 0.2 s
Insulation resistance > 1>1>1>1>1G
Ω
Ω
Arresters are designed to EN61643-11
About packing see page 65.
RAB0302-G
ø29.5±0.5
12±0.3
RAB0335-Z
M8
1.5 max.
29.7±0.3
7+0.5
32.7±0.5
48 max.
0.5)(ø15
_
ø30 max.
size
13
wrench-
RAB0275-V
ø11.8±0.2
17.4±0.5
AC Power Line Protection
Schutz von Wechselspannungsnetzen
Ueberspannungsableiter_de-en_2009.qxd 03.11.2008 16:19 Uhr Seite 54