AC Power Line Protection
Schutz von Wechselspannungsnetzen
AC Power Line Series
Protection class II & III
V10... M51-...... A8...
Type V10-A500X A80-A800XP
Ordering code B88069X4400C251 M51-A800XP B88069X5691C103
V13-A500X B88069X4781S102 A81-A800XP
B88069X4390C251 B88069X4781T502 B88069X5701S102
Protection class II II & III II & III
Application for N-PE N-PE N-PE
Nom. DC spark-over 500 800 800 V
voltage V
sdcN
DC spark-over voltage 400 ... 600 > 600 > 600 V
Impulse spark-over voltage @ 1.2/50 µs, < 1500 < 1500 < 1500 V
6 kV for 99% of measured values
(combination wave generator
[
2
Ω
Ω
])
Class II
Max. continuous operating voltage
@ 50/60 Hz 255 255 255 V
Nominal discharge current 8/20 µs 20 310kA
Max. discharge current 8/20 µs 40 320kA
Follow current @ 50/60 Hz 100 5100 A
AC discharge current 300 ––A
(TOV at 1200 V)
1 operation 50 Hz, 0.2 s
Insulation resistance > 1>1>1G
Ω
Ω
Arresters are designed to EN 61643-11.
About packing see page 65.
RAB0308-C
ø0.8
ø5±0.2
60+4
5±0.2
RAB0004-Q
60+4
ø1
6.05±0.2
+0.1
0.3
ø8
_
RAB0277-L
32± 1
M3
ø11.8± 0.2
5.8± 0.2
7.3± 0.3
17.4± 0.5