User guide

41
5.4. Syslog Messages: Severity Level Definitions
The Emergency level is the most severe type of message generated by ePowerSwitch 1G
R2
and the
Debug severity level is the least severe one.
Severity Level 0, Emergency:
The following messages appear at severity 0:
- Continuous error!
Severity Level 1, Alert:
The following messages appear at severity 1:
- Settings have been reinitialized through the serial connection
- ePowerSwitch 1G
R2
does not respond
Severity Level 2, Critical:
The following messages appear at severity 2:
- "file" config corrupted: restoring default values
Severity Level 3, Error:
ePowerSwitch 1G
R2
doesn't generate Severity Level 3.
Severity Level 4, Warning:
The following messages appear at severity 4:
- Settings have been changed through the serial connection
- Settings have been changed through the network by User "name"
Severity Level 5, Notice:
The following messages appear at severity 5:
- System has been restarted through the serial connection
- Power Supply restored
- Rule (number) : Outlet (number) has been switched ON
Severity Level 6, Informational:
The following messages appear at severity 6:
- System has been started
- Date & Time have been synchronized to a Network Time Server
- User "name" : Outlet (number) has been switched ON
- Session opened by user "name"
Severity Level 7, Debug:
ePowerSwitch 1G
R2
doesn't generate Severity Level 7.