ENGLISH
Turn o  all mounted equipment.
Disconnect Power System from power source.
How to Change Power System Batteries
Turn power system o  by holding down 
the AC Outlet Power button for 1 - 3 
seconds. Power light will shut o .
Turn both circuit breakers to "OFF".
Red 
Red 
Black
Black
BATTERY 
LEAD
Recycle battery or contact 
Ergotron for proper battery 
disposal guidelines.
BATTERY REPLACEMENT
The power module is congured for two, 33 -Ah batteries. 
Only the following batteries are compatible with this 
system:
• B&B EP33-12  • SBS S-12330
• Longway 6FM33G  • Vision 6FM33D
• Vision 6FM33HD-X  • PBQ PBQ33-12L
• Werker WKA12-33C  • Werker WKA12-35C
• Duracell Dura 12-35C
Installing batteries other than the 33 -Ah listed above will 
void the product warranty. Failure to heed this warning 
may result in severe damage to batteries, power module 
and possible re hazard.
REMPLACEMENT DE LA BATTERIE
Le module d’alimentation est conguré pour deux batteries 33 A-h. 
Seules les batteries suivantes sont compatibles avec ce système :
• B&B EP33-12  • SBS S-12330
• Longway 6FM33G  • Vision 6FM33D
• Vision 6FM33HD-X  • PBQ PBQ33-12L
• Werker WKA12-33C  • Werker WKA12-35C
• Duracell Dura 12-35C
L’installation de batteries autres que les batteries 33 A-h citées 
ci-dessus annulera la garantie du produit. Si vous ne vous conformez 
pas à cette précaution d’utilisation, les batteries et le module 
d’alimentation risquent d’être sérieusement endommagés, ce qui 
pourrait provoquer un incendie. 
WARNING
AVERTISSEMENT
822-386
www.ergotron.com
BATTERY 
LEAD
WARNING:  RISK OF ELECTRICAL DISCHARGE
• Do NOT swap battery cables, doing so will cause arcing and trip 
the circuit breaker.
• Do not remove or replace the batteries while cart is located in 
an oxygen rich or hazardous environment, arcing may occur and 
cause combustion.
• Replace  rst battery before removing second battery to reduce 
the risk of cables touching terminals and causing arcing.
• Always replace both batteries!
• Replace  rst battery before removing second battery.
• Replace batteries with same Amp/Hour rating batteries only.
• Only Ergotron-speci ed batteries may be used in the StyleView 
Power System. Please call customer care for more details.
• Recycle battery or contact Ergotron for proper battery disposal 
guidelines.
Caution: Remove Black (-) before removing Red (+).
Caution: Connect Red (+) before connecting Black (-).
 Caution: Do NOT swap battery cables, doing so will cause sparking and trip the circuit breaker.