Mostelddifcultiescanbeovercomebychecking
the following problems.
PROBLEM A
The mold doesn’t close tightly.
Check for:
1. Adjustment of handle clamps.
2. Cables out of round or bent.
3. Dirt or slag in mold parting line.
4. Correct cable size.
NOTE: Use “C” clamp if necessary.
PROBLEM B
The connection is covered with excessive slag.
Check for:
1. Welding material leaking past the disk,
caused by:
(a) Chipped graphite at tap hole.
(b) Disk moved when welding material was
dumped.
(c) Disk not properly seated.
(d) Disk was not installed.
NOTE: A small amount of slag on the surface
is not abnormal.
PROBLEM C
Molten metal “spits” out of the crucible when
making a connection.
Remedy:
1.SeeProblemD.
Field Situation Guide