Manual
22
www.erico.com
PROBLEM M
When welding to ductile iron or cast iron, the
weld does not “stick” to the surface.
Remedy:
1. Remove all coatings before cleaning.
2. Clean the surface with a rasp or grinder to bright
metal.Whengrinding,useanERICO-approved
wheel only.
3. Clean the surface with a safety solvent after
grinding or rasping.
4. Use CADWELD
®
XF-19 alloy welding material
(orange cap).
CADWELD
®
ONESHOTconnectionsdonotalways
follow the same rules as connections made with
graphite molds.
1.Noportionofthecablewithintheconnesof
the sleeve should be exposed.
2. Maximum depression under the riser (after
the slag has been removed) should be no lower
thanthebottomofthecable.Lowerllindicates
excessive leakage of molten metal or improper
positioningoftheCADWELDONESHOTmold.
CADWELD
®
ONE SHOT
Connections
Minimum
acceptable
Normal
Higher
than
normal
Field Situation Guide