RBS Product Description
Indicators Description
Local mode The RU is in local mode
Operational The RU is operational
Transmission OK Indicates state of transmission on ports A D
RF off RF not enabled
Buttons Description
TRU reset Resets the dTRU
DXU reset Resets the DXU
Local/remote mode Changes RU mode to local or remote
8 Power System
The power system of the RBS depends on the choice of power supply and may
include a number of units outside the RBS.
The RBS can be connected either to an AC power supply or to a DC power
supply.
8.1 AC Power
AC power is supplied to the ACCU through one cable for each PSU. If the power
source does not meet the AC power requirements, then filters and stabilizers
must be installed to protect the equipment and ensure proper operation.
There are two ways to connect power to the RBS, as follows:
Single phase, line to neutral
Single phase, line to line
Note: When single phase line to line is used, each supply cable requires two
circuit breakers or fuses.
Table 9 AC Power Requirements
Characteristic
Description
Voltage for specified performance
(phase voltage)
120–250 V AC
26 19/1551-LZA 701 0001 Uen PG1 | 2010-10-08