User Manual

RBS Product Description
RBS 2206 +24 V DC Fuses
Table 13 Fuse Specifications
Minimum for Safe
Function
Recommended for
Maximum Selectivity
Maximum Allowed
Fuse Rating
1 × 160 A
(1)
1 × 200 A 1 × 250 A
(1) Can be used when no transmission or optional equipment is installed.
RBS 2206 V2 +24 V DC Fuses
Table 14 Fuse Specifications
Minimum for Safe
Function
Recommended for
Maximum Selectivity
Maximum Allowed
Fuse Rating
1 × 160 A 1 × 200 A 1 × 300 A
8.3
0
48 V DC to
0
60 V DC Power
Table 15 Requirements
Characteristic
Description
Nominal
0
48 or
0
60 V DC
Range
0
40.0 to
0
72.0 V DC
Non-destructive range +0 to
0
80 V DC
Inrush current 200 A (0.1–5 ms)
RBS 2206
0
48 V DC to
0
60 V DC Fuses
Table 16 Fuse Specifications
Minimum for Safe
Function
Recommended for
Maximum Selectivity
Maximum Allowed
Fuse Rating
4 × 32 A 4 × 35 A 4 × 40 A
RBS 2206 V2
0
48 V DC to
0
60 V DC Fuses
Table 17 Fuse Specifications
Minimum for Safe
Function
Recommended for
Maximum Selectivity
Maximum Allowed
Fuse Rating
3 × 45 A 3 × 50 A 3 × 50 A
28 19/1551-LZA 701 0001 Uen PG1 | 2010-10-08