7.3 Verifying AC Mains and DC Power Supply
This section describes how to verify that the RBS has the correct incoming AC
mains and, where applicable, DC power.
Danger!
Electric shock risk. Avoid both direct and indirect contact with parts connected
to mains power as this is likely to be fatal. Switch off the mains power before
starting work.
1
Open the sunshields and the two clasps and pull the RRU to the left
side. Remove the lid from the MBU.
2
If applicable, use a multimeter to
measure the incoming AC Mains
power to the RBS and check that
it is between 100 and 127 V AC,
or between 200 and 250 V AC.
P010498A
3
If applicable, use a multimeter to
measure the incoming DC power
to the RBS and check that it is
between 40.5 and 60 V DC.
P010497A
4 Put back the MBU lid and tighten the screws.
1
11
EN
/LZT 720 0027 Uen R8A 2006-06-27