User's Manual Part 3

RBS 2308 and RBS 2309 User’s Guide
Displaying Fault I
nformation
Display fault info
rmation according to Section 10.3.1 Reading Fault Status
on page 177.
Perform the following actions step-by-step until the fault ceases:
Checking IDB Configuration
1. In the Maintenance menu in OMT, select Check IDB to display possible
inconsistencies between the HW and the IDB. Ensure that the IDB
configuration is in accordance with the HW cabinet configuration regarding
defined power system and climate system.
Checking Climate
2. Inspect the airflow path in the RBS, and ensure that the airflow is not
obstructed.
3. If the temperature is between 45 and 55° C, install a fan unit. For more
information, see Chapter Installation of RBS in this manual.
4. If the temperature is below 15°C, then the RBS must be powered with
AC. AC power is needed for the RBS to start the heater.
Note: RBS units from certain R-states are less sensitive to low temperatures
and have therefore no internal heater. For more information about unit
R-states from which these improvements apply, see chapter Product
Description, section O perating Environment in the following manual:
RBS 2308, RBS 2309, and RBS 2109
Hardware Reference M anual
EN/LZT 720 0058
Checking Incoming AC Power (Optional)
5.
Open the MBU cover and use
a multimeter to check that the
power input is either 100 V AC to
127 V AC, or 200 V AC to 250 V
AC.
P010498A
186 EN/LZT 720 0027 Uen R8A 2006-06-27