Reference Manual

Product Data RBS 2206
6.4.4 Foot Print
Unit of measurement: mm
P008315A
(RBS 2202)
RBS 2206
FRONT
99
400
598
220
45
320
400
o 20x75
Figure 51 Drilling template for RBS 2206
The RBS 2206 has the same footprint as both cabinets in the RBS 200
system, and the RBS 2202 cabinet. The base frame is used as a
template to mark new holes for the RBS 2206.
Replacements
The RBS 2206 cable interfaces are different from the RBS 200 and the
RBS 2202. New power distribution circuit breakers and new matching
power cables may have to be installed between the power distribution
board and the cabinet, see Section 6.3 Power Connections on page 110.
Make sure the existing feeders and other cables reach the radio cabinet
and that the battery back-up cables have the correct cross-sectional area.
6.4.5 Power Consumption
Table 61 Power consumption for RBS 2206
Power Supply VoltageRBS (fully
equipped)
120 - 250 V AC +24 V DC -48 V DC
Maximum power
consumption
3.9 kW/ 5.8 kW
(1)
3.2 kW 3.8 kW
(1) Power consumption during maximum battery charging.
The RBS 2206 has capacity to supply units with power up to 4.8 kW.
The power consumption during operation depends upon configuration
and traffic.
6.4.6 Heat Dissipation
All power consumed by the RBS can be considered as heat dissipation
in the RBS room.