Reference Manual

Product Data RBS 2106
bottom of the cabinet where all external power and transmission lines
from the antennas or network are brought into the cabinet.
Radio signals are connected through RF connectors. All other
connections employ screw terminals on the external side of the interface.
On the internal side, d-subs are used to access through the EMC zone.
5.3.1 AC Connection Field
N
P
E
T3
T
2
T
1
P008711A
17-28 mm
Figure 38 AC Connection Field
The AC mains supply for the RBS is connected here. The incoming
power supply can have a nominal voltage range of 120 250 V AC,
and a nominal frequency of 50 60 Hz.
Connection diagrams for various types of AC mains are given in:
RBS 2106 Installation &
Integration Manual
EN/LZT 720 0025
For more information on the RBS 2106 power system, see Section 5.4
on page 101.
EN/LZT 720 0008 P2A
2001-11-28
97 (485)
© Ericsson Radio Systems AB
All Rights Reserved