Part Numbering System
TWO POSITION ZONE VALVES, SPRING RETURN ACTUATORS
V X X X X X X X X X XX X
Body Type
T = On/Off General
S = On/Off Steam*
* High temperature actuator
must be used.
Valve Size
2 = 1/2”
3 = 3/4”
4 = 1”
5 = 1-1/4”
Options
0 = No options
A = End switch
Voltage
A = 24 Vac, 50/60 Hz
B = 110 Vac, 50 Hz and 120 Vac, 60 Hz
D = 208 Vac, 50/60 Hz
T = 277 Vac, 50/60 Hz
U = 230 Vac, 50 Hz and 240 Vac, 60 Hz
Action
1 = Spring Return Normally Closed (2- or 3-way)
2 = Spring Return Normally Opened (2-way only)
Connection Type (Availability)
1 = Sweat (1/2”, 3/4”, 1”, 1-1/4”)
2 = Threaded NPT (1/2”, 3/4”, 1”)
3 = Threaded Rp, Metric (1/2”, 3/4”, 1”)
4 = Inverted fl are (1/2”)
5 = SAE fl are (1/2”)
Cv Size
2-way 3-way Size Connection
1 = 1.0 1.5 1/2” (1, 2, 3)
3/4” (4)
2 = 2.5 3.0 1/2” (1, 2, 3, 5)
3/4” (1, 2, 3, 4)
3 = 3.5 4.0 1/2” (1, 2, 3, 5)
3/4” (1, 2, 3, 4)
1” (1)
5 = 5.0 5.0 3/4” (1, 2, 3)
1” (1)
7 = 7.5 7.5 3/4” (1, 2, 3)
1” (1)
8.0 8.0 1” (2, 3)
1-1/4” (1)
Confi guration
2 = 2-way
3 = 3-way
Actuator Type
G = On/off, General Close-off (GCO)
H = On/off, High Close-off (HCO)
Temperature Ratings
3 = General temperature
4 = High temperature
Electrical Leads
00 = 6” Motor wires
01 = Terminal block with End switch (24 Vac only)
02 = 18” (Standard) Wire leads
Cautions
When ordering valve body only: Use the fi rst six
positions to confi gure the valve.
When ordering actuator only: Use the last seven
positions to confi gure the actuator. Prefi x with
the letter A.
Inverted are fi ttings must be ordered separately.
See actuator accessories, bulletin F-26496,
for tting part numbers.
End switch is not available for 277 Vac models if
actuator temperature rating is high temperature.
Actuators with Terminal blocks require end switch
and the end switch is 24 Vac at 101 mA min. to
5A max.
End switch is 24 - 240 Vac at 101 mA min to 5A
max. and 9 to 30- Vdc at 100 mA max. for actuators
rated 240 V or less. End switch is 277 Vac at 101 mA
min. to 5A max. for actuators rated 277V.
Body and Actuator Combination: Temperature Confi gurations
Body Confi guration Actuator Spring Return Mode
VTXXXX AXX3XXXX
T = General 3 = General temperature
S = Steam 4 = High temperature
If body confi guration is T, actuator temp rating can be 3 or 4. If actuator temp rating is 3, body style must be T.
If body confi guration is S, actuator temp rating must be 4. If actuator temp rating is 4, body style can be S or T.
6