User Manual
 12  Catalog E 074441  01/06  Edition 4  www.erni.com
ERbic Profibus Ex i
There is a special Profibus specification for safety-orientated 
intrinsically safe applications. Intrinsic safety is achieved by 
limiting the energy. At low voltage, this is reflected, among 
other things, by a higher current density in the bus line, as the 
devices are also supplied with power via the bus line. 
With regard to the connector, the main factor is compliance 
with EN 50020. For example, defined clearance and creepa-
ge distances and current carrying capacity must be taken into 
account. These Ex i connectors have been developed in coo-
peration with ABB and approved for their S900 controller. The 
individual connector alone does not require separate appro-
val. This must always be given in conjunction with the system 
in accordance with the relevant directives and standards.
Electrical and mechanical characteristics
Interface connector  D-Sub, 9-pin, male
D-Sub male  Class 2
Cable termination  2 x horizontal
    1 cable outlet can be sealed with blanking plate
Cable diameter  4.5 mm (0.177”) – 8.0 mm (0.315”)
Cross section of individual conductor  Screw terminal: solid max. 1.5 mm
2
; stranded max. 1.0 mm
2
Termination type  Screw terminal
Data transmission rate  According to bus specification, 12 MBit/s
Temperature range  -20 °C – +70 °C
Permissible humidity  Max. 75 % at + 25 °C, non-condensing
Protection class  IP 40
Housing material  Thermoplast UL94V-1
D-Sub screw  #4/40 UNC, knurled with cross-head
UL approval  UL E84703 *
CE marking  ERbic connectors are passive components and do not need 
    to be identified with the CE marking according to EU direc-   
  tives.
* Due to continuous advancement, it is possible that the UL approval of a new version may not have been completed at the time of going 
to press.
Pin configuration
Terminal  D-Sub Pin  Signal
B (1)  3  RxD/TxD-P
A (2)  8  RxD/TxD-N
B (3)  3  RxD/TxD-P
A (4)  8  RxD/TxD-N
- 5  GND
-  6  VP (+5V)