B2 Flue Conguration (If less than 4m ue length is required):
If your ue system is less than 4m long (as shown in diagrams below), then a simple
aluminium exible ue is required. If you wish to install a longer ue run, up to 12m, see
section B3.
Horizontally Terminated: (utilises the escea horizontal power ue enclosure kit)
The horizontal oset of the terminal can be any amount up to the total ue length listed
below. Please consult with Esceas technical sta if your intended ue conguration steps
outside of the bounds of the ue congurations shown below.
X
Y
X + Y Maximum = 4m
Y Maximum = 1.5m
Y Minimum = 0m
X Maximum = 4m
X Minimum = 0m
X + Y Minimum = 0.4m
X
Y
X + Y Maximum = 4m
Y Maximum = 4m
Y Minimum = 0m
X Maximum = 4m
X Minimum = 0m
X + Y Minimum = 0.4m