Installation manual

630162_5EF5000InstallationGuideRemotion‐US
13.0 Checking Operating Pressure:
This appliance must be disconnected from the gas supply piping system during any
pressure testing exceeding ½ PSI (3.5 kPa)
This is done at the regulator located at the lower front of the appliance.
13.1 This must be done before the fascia has been fitted.
13.2 The manifold pressure has been factory set. Please check that the manifold pressure is as
listed below by checking at the outlet test point.
13.3 Replace operating test point screw and leak test the test point.
Propane Natural
Gas
Maximum Inlet pressure 20”wc 20”wc
Minimum inlet pressure 10”wc 5.5”wc
Manifold Pressure 10”wc 5”wc
EF5000 Pressure table
Propane
Operating pressure test point