Operation &Installation Manual The ESP Ecocent Model: ESP 400-200Ltr ESP 400-250Ltr ESP 400-300Ltr Please keep this manual safely and read it carefully before installation or operation ©ESP Ltd.
Warning!!!! Contents READ THIS BEFORE INSTALLING THE UNIT. Preface………………………………………………………………..3 All un-vented water heating systems above 15 litre (this includes the ESP Hot Water ASHP‟s) MUST be installed to meet the requirements of the Building Regulations. It is a legal requirement that the local Building Control Officer be notified of any proposed installation of un-vented water heating systems over 15 litre capacity. General Requirements………………………………………………..
Preface PLEASE NOTE FOR TRANSPORT AND STORAGE!!!: Hot water air source heat pump Storage The unit must be stored and/or transported in its shipping container in an upright position and kept dry. For transport over short distance, and provided due care is exercised, an inclination angle of up to 60 degree is permitted. Both during transport and storage, ambient temperatures of - 20 to +70 are the limits. Transport using a forklift When transporting by fork lift, the unit must remain mounted on the pallet.
1. General Requirements Hot water air source heat pump 1.
1.General Requirements Hot water air source heat pump 1.General Requirements Please be sure to use appropriate lifting equipment when moving the unit. Hot water air source heat pump 1.4 OUTLET/TERMINAL FITTINGS (TAPS, ETC.) The unit can be used in conjunction with most types of terminal fittings.
1.General Requirements Hot water air source heat pump 2.Specs A) The appropriate Building Regulations: either The Building Regulation (England), The Building Regulations (Scotland) or Building Regulations (Northern Ireland). B) The Water Fittings Regulations (England and Wales) or Water Bye laws (Scotland). C) Any other applicable Regulations. Failure to observe any of the above conditions will invalidate the warranty/gurantee. Hot water air source heat pump 2.1 APPEARANCE 1.
Hot water air source heat pump 2. Specs Hot water air source heat pump 2. Specs 2.3 DIMENSIONS 2.4 PERFORMANCE PARAMETER ESP 400 SERIES—150L/200L/250L/300LD Unit/mm Model ESP400 010-150L(D) 010-200L(D) 010-250L(D) 010-300L(D) kW 2.6 2.6 2.6 2.6 Water tank capacity L 150 200 250 300 Power input W 810 810 810 810 Running current A 3.7 3.7 3.7 3.
3.Function presentation 3.Function presentation Hot water air source heat pump Hot water air source heat pump Earthing 3.1 PLEASE NOTE: Heating capacity The unit absorbs energy from the air inlet location ambient conditions. If the air inlet temperature is low, heating capacity will show variation from standard conditions. The unit MUST be earthed and facility is provided for this in the unit design - be sure to have the unit properly earthed during installation.
Hot water air source heat pump 4. Installation 4. Installation 4.1 INSTALLATION DIAGRAM Hot water air source heat pump 4.2 PIPE FITTINGS All pipe connections to the unit are 22mm. The fittings are also threaded 3/4” BSP male should threaded pipe connections be required. Air ducts must be at least in 6 inch rigid pipe. 4.3 COLD WATER SUPPLY A 22mm cold water supply is recommended, however, if a 15mm (1/2”) supply exists which provides sufficient flow (see section 2.3) this may be used.
4 . Installation Hot water air source heat pump 4 . Installation Hot water air source heat pump Should you wish to site the Expansion Valve on the Cold Water Combination Valve this can be done by unscrewing the connection nut beneath the Expansion Valve on the Expansion Core Unit and removing the Expansion Valve. The connecting nut and blanking plug should then be unscrewed from the Cold Water Combination Valve and replaced with the Expansion Valve.
4 . Installation Hot water air source heat pump 4 . Installation Hot water air source heat pump 4.6 DRAIN TAP A draining tap should be installed in the cold water supply to the unit between the Cold Water Combination Valve (or Expansion Core Unit if being used) and the heater at as low a level as possible It is recommended that the outlet point of the drain pipe work be at least 1 metre below the level of the heater (this can be achieved by attaching a hose pipe to the drain tap outlet spigot). 4.
4 . Installation Hot water air source heat pump 4 . Installation 4.9 T&P RELIEF VALVE (“TPRV”) The TPRV is factory fitted and must not be interfered with in any way and/or removed - under NO circumstances should the installer or end user tamper with the TPRV or the warranty/guarantee will be invalidated and serious damage may occur. You will find detailed information on this safety device at Appendix 2. Hot water air source heat pump 4.
4 . Installation Hot water air source heat pump 4 . Installation Hot water air source heat pump Examples of acceptable discharge arrangements are: i. ideally below a fixed grating and above the water seal in a trapped gully. ii. downward discharges at low level; i.e. up to 100mm above external surfaces such as car parks, hard standings, grassed areas etc.
4 . Installation Hot water air source heat pump 4 . Installation Table 1 - Sizing of copper discharge pipe (D2) for common T&P relief valve sizes Hot water air source heat pump THE FOLLOWING IS FOR REFRIGERANT ENGINEER ONLY: 1) Vacuum and filling Refrigerants. The unit is supplied pre-gassed. Should a refrigerant fill be required at any point, please note the following: When you have finished the connection between the heat pump and the hot water unit, you must create a vacuum in the hot water unit.
4 . Installation Hot water air source heat pump 4 . Installation D. When you need to add the refrigerant, please do so as follows: Hot water air source heat pump IMPORTANT Do not allow any impurities to enter the refrigerant system 4) Insulation treatment As per the below picture, you must insulate all connecting pipes and you must use good quality, non flammable, PVC insulating material, of 15mm20mm thickness.
4.Installation Hot water air source heat pump 4. Installation The 2-port motorised valve MUST be wired in series with the Indirect controls (for the unit Indirect Thermostat and Thermal Cut-Out) such that the power supply to the valve is interrupted should either the Thermostat or Thermal CutOut operate. Wiring to external controls is made via the terminal block fitted. The cable should be routed through the aperture in the terminal cover and secured using cable grips.
4. Installation Hot water air source heat pump 4. Installation Hot water air source heat pump (3) Cooling in the re-circulating air mode (picture 12) Room air can be extracted from a storage room or a wine cellar, subsequently cooled and dehumidified in the heat pump and finally re-introduced into the room. Recreation rooms, boiler rooms or utility rooms are ideal installation sites. The air ducts leading through warm sections must be insulated to prevent the formation of condensation.
4 . Installation Hot water air source heat pump 5. Commissioning Installation points Hot water air source heat pump Check for obvious signs of damage to the cylinder and controls before undertaking commissioning work. 1. Decide upon the right route to be taken to move the unit; 2. Try to move the unit in its original case; 3. Be sure to have the unit and electrics fitted by qualified tradesmen. 4.
5. Commissioning Hot water air source heat pump 6. Maintenance 15) Give this manual along with the completed Log Book (if any) to the end user to retain for future reference and make the customer aware that periodic checks of the equipment are essential for safety. Hot water air source heat pump 6.1 MAINTENANCE REQUIREMENTS (The Cylinder) To ensure the continued optimum performance of the unit it should be regularly maintained.
6. Maintenance Hot water air source heat pump 6. Maintenance 6.4 DRAINING THE UNIT Switch off the electrical supply to the immersion heater(s) and heat pump. Turn off the mains water supply to the unit. Attach a hosepipe to the drain cock having sufficient length to take water to a suitable discharge point below the level of the unit, at least one metre below the unit is recommended. Open hot water tap nearest to the unit to relieve the system pressure. Open drain cock.
Failure On Flash EE8 Defrosting indicate Communication failure Defrosting 9 on 1 off EE4 Exhaust temp. protect Communication failure between wire controller and main board; 1. Shortage of refrigerant 2. Out of temp. setting too high Water level in tank too low EE3 AUX heating thermal protect 8 on 1 off EE1 1. Insufficient refrigerant 2. Block on the filter or capillary 3. Inadequate water flow 4.
6. Maintenance Hot water air source heat pump 7. User Instructions 6.9.2 The Cylinder Hot water air source heat pump 7.1 FUNCTION OF THE CONTROLLER Use of controller is as follows: 22 ©ESP Ltd.
7. User Instructions Hot water air source heat pump 7. User Instructions 4) Check parameters During running or standby state, press or rameters with the screen showing as follows: 7.2 USE OF THE CONTROLLER 1)Start up. After checking everything is OK, switch on the unit and enter into standby state, with the screen showing as follows: 2) Turn-on.
7. User Instructions Hot water air source heat pump 8. Safety Precautions 6) Malfunction Display During standby or running state, if the unit malfunctions, the system will stop and display the malfunction code as follows: Hot water air source heat pump SAFETY PRECAUTION The following are some safety tips to observe, but they are no substitute for the use of common sense! Please use the unit for the purpose intended and be sure to read, understand and follow the provisions of this manual.
8. Safety Precautions Hot water air source heat pump 8. Safety Precautions Hot water air source heat pump MOVE AND REPAIR INSTALLATION WARNING OPERATION ATTENTION OPERATION WARNING IMPORTANT: The unit warranty/guarantee will be invalidated if all work on installing, commissioning and maintaining it is not carried out by suitably qualified engineers. 25 ©ESP Ltd.
9. Guarantee Hot water air source heat pump 9. Guarantee Hot water air source heat pump The compressor in the heat pump is warranted/guaranteed for 2 years from the date of purchase. Remaining parts of the heat pump are warranted/ guaranteed for 1 year from the date of purchase. Evidence of purchase and date of supply must be submitted with any wattanty/guarantee claim. 9.
10. Spare Parts Hot water air source heat pump 10.1 SPARE PARTS Please be advised that Earth Save Products Limited carries spare parts for all the units that it supplies. We strive to ensure that spare parts are readily available at competitive prices. Please call us should you need any spare parts and we will be pleased to give you a quotation. Appendix 1 For spare parts please contact us on ++ 44 (0) 844 414 2345 / ++ 44 (0)1235 815569 or ++ 44 (0)1865 40 72 70 .
UNVENTED HOT WATER STORAGE SYSTEMS AND CONTROLS The purpose of this guide is to provide useful information on Unvented Hot Water Storage Systems and their benefits, the features and functions of the typical controls used. How the Unvented System Works The basic difference between the high pressure Unvented Systems and a traditional low pressure vented system is that we no longer require the cold water storage cistern, open vent pipe or cold feed pipe.
UNVENTED HOT WATER STORAGE SYSTEMS AND CONTROLS The significant benefits to be gained from the installation of an Unvented Hot Water Storage System can be divided into two categories; benefits to the Specifier/Installer and benefits to the householder. Householder Benefits • Superior performance - ensures constant high flow rates at all outlets and allows rapid filling of baths. • Balanced pressures - far wider choice of continental style taps and showers can be used.
UNVENTED HOT WATER STORAGE SYSTEMS AND CONTROLS A recent development now available in the UK is the Combi Storage unit. This type of unit incorporates the benefits, features and controls associated with Unvented Systems but has a limited storage capacity of hot water. Bubble-Top Units Bubble-Top units, manufactured from either copper or stainless steel, accommodate the expansion of the heated water by using an internal air-bubble which is generated and trapped at the top of the unit during commissioning.
UNVENTED HOT WATER STORAGE SYSTEMS AND CONTROLS Originally supplied as separate components, Reliance have developed and engineered these controls to form a one piece or two piece Inlet Control Group for units requiring DN20 Nominal size controls and, a three piece Inlet Control Group for units requiring DN25 size controls.Inlet Control Group One Piece (Multibloc).
UNVENTED HOT WATER STORAGE SYSTEMS AND CONTROLS Inlet Control Group - Two Piece (Core Unit) Inlet Control Group - Three Piece (Check Valve Manifold) Forerunner of the Multibloc one piece control, this Inlet Control Group is again used on all types of Unvented Systems and comprises of a separate Pressure Reducing Valve/Strainer and combined Check/Expansion Valve core unit offering the following features.
UNVENTED HOT WATER STORAGE SYSTEMS AND CONTROLS All Reliance Inlet Control Groups are supplied with comprehensive Installation and Maintenance instructions to supplement the relevant Unvented System manufacturer‟s Instructions. All potable Expansion Vessels with a nominal capacity of 16 litres or greater incorporate a replaceable membrane to facilitate replacement in the unlikely event of failure.
UNVENTED HOT WATER STORAGE SYSTEMS AND CONTROLS The Temperature & Pressure Relief Valve is the third and final level of protection. Although this valve does incorporate a pressure relief function, the sole purpose of this control is to prevent the system water temperature exceeding 99° C - the pressure relief function is not used.
UNVENTED HOT WATER STORAGE SYSTEMS AND CONTROLS Spare Components Problems and Remedial Action The Inlet Control Groups supplied by Reliance for use with Unvented Systems have proven to be extremely reliable in field service but, in the unlikely event of failure, the following spare components are available from the relevant manufacturer of the Unvented System in question.
TPR15 Pressure and Temperature Relief Valves Appendix 2 Product Specification Sheet TPR15 Pressure and Temperature Relief Valves A compact, cartridge type pressure and temperature safety relief valve for use on unvented hot water systems. Uses Product Features and Benefits • Fully approved by WRAS for use on unvented hot water systems. • Available in a wide range of relief pressures between 4.0 and 10 bar.
TPR15 Pressure and Temperature Relief Valves Description The new Reliance compact pressure and temperature relief valve has been designed to provide protection against over pressurisation which can occur within an unvented hot water system if the input temperature controls fail. The valve is designed to be fitted in the upper portion of the cylinder as this is where the hottest system temperatures will be found.
Model No: TPR15 Pressure and Temperature Relief Valves Date of Purchase: Specifications Pressure relief tolerance: +/- 5% Temperature relief: 90°C - 95°C Discharge capacity: 10Kw Any work carried out post commissioning: Date Nature of work carried out How to Specify AWRAS Approved pressure and temperature relief valve for use on unvented systems to protect to EN1490 (select appropriate range code).