Specifications

  – 13 –  ETAsys.com
Specifications are subject to change without notice.
1601 Jack McKay Blvd. • Ennis, Texas 75119  U.S.A.
Telephone: 800-321-6699 • Fax: 800-996-3821
TECHNICAL DATA
Current Rating    15 amps 
Operating Voltage    102 - 132VAC 
High Voltage Surge Protection   Trigger at 133VAC, 1ms Typically
Low Voltage Protection    Trigger 101VAC, 1ms Typically
Voltmeter Accuracy     ±1.5VAC
Spike Protection Modes   DCS(DualClampingSuppression)CircuitryonincomingACMainsandEachSequential
Section Output
Min. Spike Clamping Voltage   460VRMS@3,000A
Max. Spike Clamping Voltage    6000V
Max. Spike Clamping Resp. Time   1 nanosecond
Spike Clamping Voltage @ 100A   1250Vp for 20µs
Maximum surge current    6,500A
Energy Rating @ 2ms    2000 Joules
Noise Attenuation EMI/RFI  
Seq. Section 1 & 2  10dB@10kHz 
40dB@100kHz 
100dB@10MHz
Temperature Range   5° to 35°
C
Humidity Range   5%to95%R.H.
Power Consumption  12 Watts
MECHANICAL
Chassis Finish  Black
Mounting    Rack Mount, 19", 1RU
DIMENSIONS    
Height   1.75" (1RU, 45mm)
 Width   19" (216mm)
 Depth   8.5" (549mm)
Weight  7.6lbs (3.45kg)
Agency Listings  MET(UL1449Code)
ETA-ECS3 
Power Sequencer & Conditioner