Datasheet
Thermal Overcurrent Circuit Breaker 1410-L2/G1
www.e-t-a.com06/07
1 - 49
1
Description
Typical applications
Ordering information
Approvals
Technical data
Single pole press-to-reset thermal circuit breaker with extremely fast
overload switching performance (R-type TO CBE to EN 60934). Single
hole threadneck, PCB or integral mounting with a choice of designs.
Miniaturised construction minimises PCB real estate required. Type
1410-L2 and 1410-G1 versions feature changeover contacts suitable for
providing status output signals. Largely temperature-insensitive.
Motors, transformers, solenoids, PCBs, hand-held machines, appliances,
instrumentation.
1410-L2... 1410-G1...
Authority Voltage rating Current ratings
VDE AC 240 V 0.63...10 A
DC 50 V 0.63...2 A
DC 28 V 2.5...10 A
UL, CSA AC 250 V; DC 50 V 0.63...10 A
Standard current ratings and typical internal resistance values
Type No.
1410 single pole circuit breaker
Configuration
L PCB mounting or integral mounting
G threadneck panel mounting or PCB mounting
Mounting
1 threadneck 3/8-27UNS-2A (1410-G)
2 PCB 10.15x7.62 (1410-L)
3 PCB 10.15without shunt terminal (1410-L)
Number of poles
1 1-pole, thermally protected
Hardware
0 without
1 with hexnut and knurled nut (only1410-G)
> 5 pcs hexnut and knurled nut bulk shipped
2 without hexnut and knurled nut and without shunt
terminal (only 1410-G)
4 with hexnut and knurled nut,
without shunt terminal (only 1410-G)
8 with actuator guard and marking CB..
(only 1410-G)
Terminal design
L2 solder pins 1x0.8 silver-plated
P2 blade terminals DIN 46244-A2.8-0.8 silver-plated (only -G)
P3 blade terminals DIN 46244-A4.8-0.5 silver-plated (only -G)
Characteristic curve
F1 fast acting
Actuator
B flat reset-slide (only 1410-G)
S reset slide/button
Actuator colour
01 black (for -G1..)
02 white (for -L2..)
04 red (for 1410-G..-...B)
Current ratings
0.63...10 A
1410 - L 2 1 0 - L2 F1 - S 02 - 0.8 A ordering example
*mounting hardware bulk shipped
Current Internal Current Internal
rating (A) resistance (Ω) rating (A) resistance (Ω)
0.63 1.8 3.15 < 0.12
0.8 1.7 4 < 0.1
1 1.3 5 < 0.1
1.5 < 1 6.3 < 0.1
1.8 < 1 8 < 0.1
2 < 1 10 < 0.1
2.5 < 0.15
For further details please see chapter: Technical Information
Voltage rating AC 240 V; DC 28 V
(UL: AC 250 V; DC 50 V)
Current rating range 1-2 0.63...10 A
Auxiliary circuit 1-3 0.2 x I
N
max. 1 A, AC 250 V
Typical life
AC 240 V: 0.63...2.25 A 500 operations at 2 x I
N
, inductive
2.5...10 A 500 operations at 2 x I
N
, resistive
DC 50 V: 0.63...2.25 A 500 operations at 2 x I
N
, inductive
DC 28 V: 2.5...10 A 500 operations at 2 x I
N
, inductive
Ambient temperature -20...+100 °C (-4...+212 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 1,500 V
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity I
cn
0.63...2 A 12 x I
N
(o-o-o) 2.5...8 A 8 x I
N
, AC max. 50 A
10 A 6 x I
N
, AC
3.15...10 A 10 x I
N
, DC
Interrupting capacity 0.63...10 A 2,000 A AC 250 V
(UL 1077) 0.63...10 A 200 A DC 50 V
Degree of protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP00
Vibration 8 g (57-500 Hz) ±0.61 mm (10-57 Hz),
to IEC 60068-2-6, test Fc,
10 frequency cycles/axis
Shock 20 g (11 ms)
to IEC 60068-2-27, test Ea
Corrosion 48 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity 96 hours at 95 % RH
to IEC 60068-2-3, test Ca