Certificate
DQD 507 Rev. 2012-05-22 Page 1
Certificate of Compliance
Certificate: 1648301 Master Contract: 165971
Project: 70130605 Date Issued: 2017-04-06
Issued to: E-T-A Circuit Breakers Limited
1551 Bishop Court
Mount Prospect, Illinois 60056
USA
Attention: Timm West
The products listed below are eligible to bear the CSA Mark shown
with adjacent indicator
Issued by:
Steven Jeffery
PRODUCTS
CLASS - C321530 - SUPPLEMENTARY PROTECTORS-COMPONENT ACCEPTANCE PROGRAM
For details related to rating, size, configuration, etc. reference should be made to the CSA Certification Record or
the descriptive report.
Supplementary protectors, thermal-magnetic trip, manual reset, with manual switching feature, with or without
auxiliary contacts, trip-free mechanism - Series 2210, suffix S and T, 1 to 4-pole, 32A and less, 277V ac and less,
65V dc and less, 277/480V ac.
Application code:
Trip current (TC): TC1, (135 % of marked ampere rating)
Overload rating (OL): OL0 (1.5 time of marked ampere for general use.
Short circuit rating (SC):
277 AC
0.1
-
16
5KA, C, 1
277 AC
18
-
32
2KA, C, 1
65 DC
0.1
-
32
2KA, U, 1
277/480 AC
0.1
-
16
5KA, C, 1
277/480 AC
18
-
32
2KA, C,
1
APPLICABLE REQUIREMENTS
CSA C22.2 No 235-04 - Supplementary Protectors