User Manual
2 The Retrofit 11
Step 9: With the tabs fully inserted in the 
sides of the rack, pull the 
backplane towards the front of 
the rack to line up the screw 
holes in the upper side corners 
to line up. 
Step 10: Install one screw with a sleeve in 
the upper-corner (for single-
height backplanes) or the middle 
of the rear edge (for dual-height backplanes) of each side of the backplane.
Step 11: Connect Panic In, Panic Out and External Beacon to the CEM3 screw terminal 
block.
Backplane Settings
Upgrade kit backplanes ship from the factory with all DIP switches in the off (down) position. 
You will have to set the DIP switches on the new backplane to match your rack. You will 
also have to verify the termination switch settings.
a: Set both termination switches to “Off” (middle position) for all racks except the 
last rack in your system.
b: Set the termination switches for the last rack in the system to “ON” (top 
position).
c: Using a precision screwdriver, set the DIP switches to match your rack type 
according to:
• number of modules (12, 24, 36, or 48)
• whether the rack has Advanced Features (AF)
• whether the rack is a neutral disconnect rack
Use the following chart to determine your required DIP switch settings:
Note:
You cannot use the screws without the additional shoulder-sleeve as they will 
block the CEM3 from being fully inserted.
DIP switch Number
Rack Model 12345678
ESR3-12 On On
ESR3-12N On On On
ESR3-12AF On On On
ESR3-12AFN On On On On
ESR3-24 On On
ESR3-24N On On On
ESR3-24AF On On On
ESR3-24AFN On On On On
ESR3-36 On On
ESR3-36N On On On
ESR3-36AF On On On
Screw with 
sleeve
Single height backplane shown
Set termination to “Off”
(middle position)
Set DIP switches
Emergency Contact 
(Panic) switch