User Manual
3 Land Load Wires 13
Chapter 3
Land Load Wires
Land Load Wires
Each dimmer has three sets of lugs connected to phase, 
neutral and earth. Phase and earth lugs are on the right side 
of the rack, neutral lugs are on the left. Lugs can be single 6/
10/15/25 amp, paired 15/25 amp fluorescent, or double-
height 50 amp.
Step 1: Route the load wires to the rack(s).
Step 2: If using Multicore cable, strip back the sheath so 
Note:
When using ED15AFRF modules connected to 
dimmable fluorescent 3-wire ballasts, wire the top 
lug in each slot to the ballast’s non-dimmed power 
lead and the bottom lug to the dimmed ballast 
control lead.
CAUTION:
 Dress and terminate wires neatly and avoid leaving 
extra wire inside the rack. Too much clutter 
(especially along the right side of the rack) can 
restrict air circulation and reduce cooling efficiency. 
If cabling interferes with airflow during operation, 
the rack may shut down due to overheating.
Load wires should not cross between racks. They 
should enter the rack in which they will be 
terminated.
Phase and neutral load wiring must follow the same 
conduit/path for each circuit.
Figure 10: Line and 
load wiring example
Dress and connect load 
wires neatly without leaving 
extra wire in the rack.
Double-height 50 amp lug
6/10/15/25 amp lug
Dual 15/25 amp lugs (fluorescent)
Switched
Control or 
Dimmed
Figure 11: Load lug types










