Converting Neutral Disconnect Slots
There are two classes of modules available for Sensor3 CE racks - modules which break 
the neutral, such as RCD or ND modules, and single pole modules that do not. Normally 
your rack will be configured by ETC at the factory for the correct module types, however if 
you have a mixture of modules or you have not been able to supply details of slot 
allocations you may need to configure some slots on site.
Step 1: Determine which dimmer slots you will be converting. You can convert either 
individual slots or a three-slot strip at a time.
Step 2: Gently bend the neutral lug retraining tab out with a 
small flat blade screwdriver until the lug releases and 
you are able to pull it out. See Figure 15.
Step 3: Use a flat blade screwdriver to loosen the threaded 
inserts until the contact plates can slide out of both 
lugs.
Step 4: Repeat Step 2 and Step 3 for the other dimmer slot 
lug.
Step 5: Install a Neutral lug jumper into the lugs and tighten 
the threaded inserts.
Step 6: Slide the jumpers into the plastic lug strip until the lug tab clicks into place.
Step 7: Secure the jumper to the thread on the Neutral bus bar using the provided 
M3x8mm screw.
Repeat Steps 1 through 6 for any other lugs you want to convert
CAUTION:
Lug catches will break if bent too far. Only bend the 
catch until the lug releases.
Figure 15: Removing a lug 
Use a small flat screwdriver 
to lift the lug tab enough to 
release the lug from the strip 
and pull it out.
Figure 16: Converting Neutral Disconnect lugs to use single pole dimmers