If desired, a remote switch can be wired to the CEM3 backplane to control CEM3 selection 
in racks equipped with ETC’s Redundant Tracking CEM3 option.
Step 1: Pull 1.5mm
2
 wires between your remote switch and the CEM3 backplane 
through the data cable conduit. See Running DMX Cable to Racks, page 20 for 
data conduit installation details. For systems with no requirement for remote 
tracking status indication three wires are required, otherwise four wires will be 
required.
Step 2: Connect the remote switch wires to the J12 connector on the rear of the 
backplane.
Step 3: Wire the remote switch and indicator to the J12 connector according to 
Figure 26.
Note:
You must supply your own enclosed single-pole double-throw center-off switch to 
install a remote select switch. You may optionally use an external 24V DC power 
supply, or use the power supply from the rack backplane.
Note:
The J12 connector is a removable plug header and is easier to wire when it is 
disconnected from the backplane in an installed rack.
1 2 3 4+24Vdc COM
J12
Figure 26: J12 Dual Tracking remote connector wiring
Header at the top of the 
backplane PCB
Orange remote tracking header.
Pin 1 is the pin closest to the phase 
bars (left side of the rack as you look 
in)
Position A - Primary
Position B - Secondary
An indicator lamp 
50mA 24Vdc max for 
internal power supply