User guide

ETC Installation Guide
Unison Paradigm
®
Occupancy Sensor
Occupancy Sensor Installation Guide Page 1 of 8 Electronic Theatre Controls, Inc.
Corporate Headquarters
3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA
Tel +608 831 4116
Fax +608 836 1736
London, UK
Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK
Tel +44 (0)20 8896 1000
Fax +44 (0)20 8896 2000
Rome, IT
Via Pieve Torina, 48, 00156 Rome, Italy
Tel +39 (06) 32 111 683
Fax +44 (0)20 8752 8486
Holzkirchen, DE
Ohmstrasse 3, 83607 Holzkirchen, Germany
Tel +49 (80 24) 47 00-0
Fax +49 (80 24) 47 00-3 00
Hong Kong
Rm 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong
Tel +852 2799 1220
Service:
(Americas) service@etcconnect.com
(UK) service@etceurope.com
(DE) techserv-hoki@etcconnect.com
(Asia) service@etcasia.com
Web:
www.etcconnect.com
Copyright © 2013 ETC. All Rights Reserved.
Product information and specifications subject to change.
7184M2160
Rev B
Released 2013-01
ETC intends this document to be provided in its entirety.
Overview
The Unison Paradigm
®
Occupancy Sensor is a ceiling mounted sensor that utilizes
passive infrared (PIR) technology; providing reliable vacancy and occupancy
detection for lighting control. Paradigm Occupancy Sensors integrate with Paradigm
lighting control systems, providing energy efficient lighting control solutions.
Wire Specification
The Paradigm Occupancy Sensor utilizes LinkConnect to power the sensor and to
provide data to and from the connected Paradigm control system. LinkConnect is
topology-free and polarity independent. You can install your data runs in any desired
combination of bus, star, loop, and home-run. ETC recommends using Belden 8471
(or equivalent) wire. The total combined length of a LinkConnect wire run may not
exceed 1,640 feet (500m), with a maximum distance of 1,312 feet (400m) between
any two devices.
All control wiring should be installed and terminated by a qualified installer and should
follow standard wiring installation practices, and meet local codes. Leave
approximately 10 inches (254mm) of wiring in the junction box or tied back in the
ceiling to allow for wiring connections and future service needs.
Note:
ETC requires that all sensors be grounded by using a 14 AWG
(2.5mm
2
) ESD drain wire.
The Paradigm Occupancy Sensor provides 360 degree coverage
of the installed location and is available in three models:
P-OCC-SR- Occupancy Sensor with small room lens covers 450 sq. ft.
at 8 ft./ 800 sq. ft. at 10 ft.
P-OCC - Occupancy Sensor with standard room lens covers
1,800 sq. ft. at 8 ft./ 3,000 sq. ft. at 10 ft.
P-OCC-HC - Occupancy Sensor with high ceiling lens covers 300 sq. ft.
at 10 ft./ 7,000 sq. ft. at 40 ft.
Each sensor is available in neutral white or black finish. Lens
masks are provided to allow customized occupancy detection
fields as required by each installation.

Summary of content (8 pages)