Operation Manual
39
EN
How you select the function you want
is described in the How to set the ther-
mostat/Control functions section.
Floor thermostat - A sensor in the oor meas-
ures the temperature and then regulates
the heating accordingly. If the oor sensor
is connected when the thermostat is turned
on for the rst time, this function is selected
automatically. The preset value is 22°C.
Room thermostat - the thermostat has
built-in sensors for measuring the room’s
temperature and controlling the heating.
The control function cannot be selected
when the oor sensor is connected.
Room and oor thermostat - The built-in
sensor regulates the room temperature
and the sensor in the oor functions as a
oor temperature limiter. The limitation
can be set to between 5°C and 45°C. The
factory setting of 35°C gives a surface
temperature of approx. 27°C. The cut-out
temperature can be changed, see the
How to set the thermostat/Temperature
section.
Important
In rooms with large windows that are ex-
posed to solar insolation, we recommend
the Room and oor thermostat function.
In rooms with wooden ooring, the
Room and oor thermostat function
must always be used.