fixed end. The gap of the 2 joints should be less than 1/16”.
Deburr the cut. You will need to drill the last hole about the same
distance as the other end.
Greasing Casters & Bearings: Using a synthetic grease, grease
all casters. Mobil 1 synthetic is recommended, do not use a
lithium grease.
NOTE: Some casters may not have grease fittings. These will be
sealed bearings and will not require grease.
Final Leveling of Table: Lower all ½-13 leveling screws. Once
you have the table with the floor flange and wear strip mounted,
install all remaining screws to the spacer plate and tighten. Once
this is done, place shim plates in the center of the TT and level
screws in the center of TT. Plug in the fiber optic cable and secure
with tie wraps to a leveling screw.
Setting Mechanical Limits: Make sure that the mechanical limits
have been set for proper amount of travel. It is standard to set the
limits where the table has about 45 degrees of over-travel in each
direction. Adjust as needed by turning the proper knob for the
direction of travel.
Application Of Conductive Grease: Attach the turntable top.
Using the TT controller, position the table to the 0 degrees
position. Make a straight line from the table to the flange to verify
the encoder count and positioning of table. Then start the table in
scan mode. Using a syringe, squeeze the contents of one tube of
GC Electronics conductive grease into the barrel. While table is
rotating slowly apply grease to the grounding brushes. Apply one
tube per meter size of the diameter of the table. Run table for
approximately 1 hour to validate proper operation and allow
sufficient lubrication of moving parts.