ETS-Lindgren Inc. reserves the right to make changes to any product described herein in order to improve function, design, or for any other reason. Nothing contained herein shall constitute ETS-Lindgren Inc. assuming any liability whatsoever arising out of the application or use of any product or circuit described herein. ETS-Lindgren Inc. does not convey any license under its patent rights or the rights of others. © Copyright 1999–2014 by ETS-Lindgren Inc. All Rights Reserved.
Table of Contents Notes, Cautions, and Warnings ................................................ v 1.0 Introduction .......................................................................... 7 Data ............................................................................................................ 7 ETS-Lindgren Product Information Bulletin ................................................. 8 2.0 Maintenance .........................................................................
This page intentionally left blank. iv www.ets-lindgren.
Notes, Cautions, and Warnings Note: Denotes helpful information intended to provide tips for better use of the product. Caution: Denotes a hazard. Failure to follow instructions could result in minor personal injury and/or property damage. Included text gives proper procedures. Warning: Denotes a hazard. Failure to follow instructions could result in SEVERE personal injury and/or property damage. Included text gives proper procedures.
This page intentionally left blank. vi www.ets-lindgren.
1.0 Introduction The ETS-Lindgren Model 3816/2 Line Impedance Stabilization Network (LISN) is a two-channel low pass filter network designed to isolate the Equipment Under Test from an external power source while steering any radio frequency signals from the power line to a 50-ohm port. Model 3816/2 Front View The conducted emissions measurements may be made in accordance with regulatory compliance standards.
ETS-Lindgren Product Information Bulletin See the ETS-Lindgren Product Information Bulletin included with your shipment for the following: 8 Warranty information Safety, regulatory, and other product marking information Steps to receive your shipment Steps to return a component for service ETS-Lindgren calibration service ETS-Lindgren contact information Introduction www.ets-lindgren.
2.0 Maintenance Only trained service personnel should perform adjustments and/or service procedures. Inside the Model 3816/2 are LETHAL voltages with which you could come into contact. Capacitors inside the unit may still be CHARGED even when the unit is disconnected from power. Before performing any maintenance, follow the safety information in the ETS-Lindgren Product Information Bulletin included with your shipment.
Service Procedures For the steps to return a system or system component to ETS-Lindgren for service, see the Product Information Bulletin included with your shipment. 10 Maintenance www.ets-lindgren.
3.
Environmental Installation: Indoor use only Altitude: 15000 ft (4572 m) max Temperature: 0°C to 40°C (32°F to 104°F) Relative Humidity: 80% up to 31°C (87.8°F) decreasing linearly to 50% at 40°C (104°F) Physical Specifications 12 Height: 124 mm (4.9 in) Width: 218 mm (8.6 in) Depth: 381 mm (15.0 in) Weight: 5.4 kg (12.0 lb) Specifications www.ets-lindgren.
4.0 Installation and Application Before connecting any components, follow the safety information in the ETS-Lindgren Product Information Bulletin included with your shipment.
The input power connection is made through a three-wire power cord utilizing the accepted international color code. The input power cord opening is sized to accept a standard electrical conduit fitting or strain relief (supplied). An internally-mounted terminal strip provides the input connection point. When connecting the conduit, disconnect the power cord from the terminal strip and remove it.
LINE SELECT SWITCH Select the line to be monitored by the three-position selector switch. The line not selected is internally terminated into 50 ohms. When using the remote (center) position, connect the monitored line to the 9-pin connector on the rear panel. Control signals are low-level 5 volt DC. To monitor Line L1, apply +5VDC to pin 1 of the 9-pin connector. To monitor L2, apply +5VDC to pin 3.
Back Panel Connectors POWER INPUT The input power connection is made through a jacketed three-conductor power cable. This three-conductor power cable is rated at 16 amperes maximum. In case of emergency, power can be removed from the unit by disconnecting the Model 3816/2 input power plug from the power mains. Alternately, a properly rated circuit breaker or switch which removes mains power from the unit can be installed in proximity to the unit. RF GROUND See description on page 14.
5.0 Schematic Resistance values shown in ohms. Ground choke select switch (S1) shown in the IN position. Line monitor select switch (S2) shown in the L2 (NTL) position. NEMA type output connector shown. www.ets-lindgren.
Schematic www.ets-lindgren.
Appendix A: Warranty See the Product Information Bulletin included with your shipment for the complete ETS-Lindgren warranty for your Model 3816/2. DURATION OF WARRANTIES FOR MODEL 3816/2 All product warranties, except the warranty of title, and all remedies for warranty failures are limited to two years. Product Warranted Duration of Warranty Period Model 3816/2 Line Impedance Stabilization Network (LISN) 2 Years www.ets-lindgren.