Operating instructions
20 ETS WAGO-Software
WAGO ETS Plug-in
Manual
2.0.0
3.7 Importing a Symbol File in the ETS Plug-in
Specific configurations are required to operate the KNX Module and the KNX IP
Controller. The WAGO-I/O-PRO software generates these configurations and
exports them to an “SYM_XML” icon file.
In the Plug-in window:
1. Click [File] in the main menu of the plug-in user interface.
2. Select the Import SYM-XML file… menu item.
Figure 9: “Import SYM-XML file…” menu item
3. In the “Select SYM-XML file for this device” window, select a SYM_XML
file containing the specific configuration of the KNX Module or KNX IP
Controller.
Figure 10: “Select SYM-XML file for this device” dialog
A checkbox is provided below the entry field for the source file.
• If the box is unchecked, the device configuration is overwritten with the
data in the SYM_XML file.
• If it is checked, the current device configuration is synchronized with the
settings specified in the SYM_XML file.