If a node contains several KNX Modules, the DPTs of all bus modules are
contained in the SYM_XML file. In this case, proceed as follows:
4. In the Module index selection field (“Settings” area), select the KNX
Module number for the DPTs to be imported.
5. Click [Update] to start the synchronization.
Observe the index counting method and designation!
If a second KNX Module of this type is used on a KNX IP Controller (750-889),
it will operate in device mode. The first KNX Module is automatically set to
router mode. Although the first KNX Module cannot be accessed via the IEC
application, the second KNX Module is addressed via index 2 (see also the
manual of the KNX IP 750-889 Controller).
The selected module index influences the naming of the network variables (see
Section “Network Variables”).
Configure KNX Modules individually!
Several KNX Modules cannot be configured at the same time.