4.1.1.1.2 Exporting a Configuration as a CSV File
CSV file does not contain a fully specified configuration!
Unlike an XML file, the CSV file does not contain a fully specified configuration.
It is therefore not suitable as a backup file.
1. In the main menu choose File > Export > CSV.
2. Enter a storage location in the opened dialog.
3. Left-click [Save] to save the configuration and close the dialog.
Simple editing of group address associations and other properties of network
variables!
You can edit the properties of network variables with Excel or a text editor. Many
text fields start with an additional blank space in order to prevent accidental
automatic Excel conversions.
After editing, be sure to save the file again in *.csv file format.
4.1.1.1.3 Import XML File (Backup Restore)
1. In the main menu, choose File > Import > XML (Restore).
2. Search for the required XML file in the dialog that opens.
3. Left-click [Open] to import the configuration file and close the dialog.
4. A warning prompt indicates that importing a configuration will overwrite all
existing settings and assignments. If you agree, click the [Yes] button.
Retain settings via the ETS Import/Export function (XML)!
The export or import function (XML) enables you to recover previous settings
after a new installation of the ETS, or to load them another PC.