Operating instructions
38 KNX/EIB/TP1 Module / KNX IP Controller Parameterization WAGO-Software
WAGO ETS Plug-in
Manual
2.0.0
Figure 26: Multiple selection for editing network variables
4.1.6 Status Bar
The “Assigned group addresses” percentage bar is shown on the right of the status
bar. This indicates the relative usage of the ETS Plug-in based on the following
limits:
• 253 communication objects for the configuration of controller and modules
• 254 group addresses for the configuration of controller and modules
• 254 associations for the configuration of controller and modules.
Usage is stated as a percentage of the specified capacity. It is displayed as a green
bar.
Figure 27: “Assigned group addresses” percentage bar (example)
Example:
The system is at full capacity when there are 253 communication objects or 254
group addresses or 254 associations present.
If two communication objects with 127 group addresses each are connected, this
makes 254 associations. The system is then at full capacity.
No further assignments are possible with 100 % rate of usage.