Operating instructions
WAGO-Software KNXnet/IP Router Parameterization 45
WAGO ETS Plug-in
Manual
2.0.0
Incorrect entries will not be saved!
Incorrect entries are not saved in the system!
Watch for different project numbers!
The project number in the “Extended Device Parameters” dialog is not identical
to the project number assigned in the ETS.
Bus power failure and return are reported via KNX!
If a power failure is detected on the bus line, the error is output as a KNXnet/IP
telegram. Power restoration is also indicated via KNXnet/IP.
Exception: Bus power failure and return are not reported if you select the
“locked” option for Voltage monitor.
Specify tunneling address!
Enter in the Settings tab of the ETS Properties menu a physical address
(tunneling address) for communicating with KNX devices. Alternatively, this
setting can also be made via the WBM of the controller.
Tunneling address must originate from the router line!
The physical address (tunneling address) must originate from the line that the
KNXnet/IP Router will be connected to.
Example:
Line: 1.3
Physical address: 1.3.XXX,
where X must be a number between 0 and 255.
Ensure uniqueness of physical addresses!
The physical address (tunneling address) is not managed by the ETS. For this
reason, the ETS cannot prevent a double assignment of the same physical address
and it is recommended that an address in the upper value range is used (e.g.,
1.1.254).